Instruction 3015-4275 
Acknowledging Alarms 
Each pending alarm may require, depending upon selected alarm mode, acknowledgment before the system 
returns to normal operation (refer to Alarm Ack Mode
11
 on Page 38). To acknowledge an alarm, navigate to the 
Alarm Detail Screen and press the ACK key as previously described. You will then be returned to the Alarm 
Summary Screen
 and the box associated with that alarm will no longer be blinking, indicating that the alarm 
has been acknowledged. Repeat this procedure to acknowledge any remaining alarms. 
Alarm Summary Screen (Acknowledge Mode) 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Once all the alarms associated with a given AGM300 are acknowledged, its red ALARM LED will turn off and 
any external alarms connected to the AGM300 relays will de-activate. All pending alarms across the entire 
network must be acknowledged before the ADM800 returns to normal operation. Once that occurs, its red 
ALARM LED will turn off and any associated external alarms connected to the ADM800 relays will de-activate. 
Keep in mind that the system will continue to generate new alarms if PPM values above the alarm thresholds 
are detected.