Instruction 3015-4275 
Clearing System Faults 
If the fault condition is associated with an AGM300, the monitor will return to normal operation soon after the 
problem is corrected. At that time the YELLOW LED will turn off and any external alarms connected to the 
monitor’s alarm relays will also turn off. The ADM800 will return to normal operation the next time it polls the 
affected AGM300 monitor. 
Once the system malfunction has been corrected it may take some time for the fault condition to clear 
completely.  If the fault is associated with a specific zone, the AGM300 must first cycle back to the affected 
zone before it returns to its normal operating mode. At that time the yellow FAULT LED will turn off and any 
external alarms connected to the AGM300 unit will de-activate. The ADM800 will return to normal operation the 
next time it polls the affected monitor. 
Viewing Fault Log 
A data log of the last 20 fault conditions is retained in memory. From the Fault Screen (Page 54) press the 
LOG key to view a display of the fault log.  
Fault Log Screen 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
This screen lists potential fault conditions in the left column and displays a check mark indicating which 
problems were associated with each fault condition as represented by the vertical cursor bar. As you move the 
bar horizontally using the LEFT/RIGHT cursor keys, the date and time the fault condition was detected is 
displayed in the upper right hand corner of the display window. 
Anytime the fault status changes, there is an entry in the fault log, both when the fault occurs and when it is 
cleared.