IntelliKnight 5820XL Installation Manual
3-10
151209
3.6.3
Current Draw Worksheet for Hochiki SLC Devices
Use Table 3-2 to determine current requirements during alarm/battery standby operation when 
Hochiki SLC devices are installed. You can install up 127 Hochiki devices per loop (508 max 
per panel). Copy this section if additional space is required.
Table 3-2: Current Draw Worksheet for Hochiki SLC Devices
Device
# of Devices
Current per Device
Standby 
Current
Alarm 
Current
For each device use this formula:      This column      X      This column               =      Current per number of devices.
IntelliKnight 5820XL Fire Panel 
(Current draw from battery)
1
Standby:
215 mA
215 mA
Alarm:
385 mA
385 mA
Addressable SLC Devices
SD500-AIM
(508 max.)
1
 
Standby/Alarm:
0.55 mA
mA
mA
SD500-MIM
mA
mA
SD500-PS
SD500-ARM
mA
mA
SD505-AHS
mA
mA
SD505-AIS
mA
mA
SD505-APS
mA
mA
SD500-ANM
(508 max.)
1
Aux. Pwr
Standby:
8 mA
mA
Alarm:
60 mA
mA
SLC
Standby/
Alarm:
.55 mA
mA
mA
SD500-SDM
(508 max.)
1
SLC
Standby/
Alarm:
.55 mA
mA
mA
Aux. Pwr
Standby:
20 mA
mA
Alarm:
106 mA
mA
SD500-LED
(100 max.)
1
Aux. Pwr
Standby:
10 mA
mA
Alarm:
220 mA
mA
LED:
10 mA
mA
mA
SLC
Standby/
Alarm:
0.55 mA
mA
mA
SLC Accessory Bases
SD505-6RB
(508 max.)
Standby/Alram:
.082 mA
mA
mA
SD505-6SB
(508 max.)
Aux. Pwr
Standby:
1 mA
mA
Alarm:
32 mA
mA
SLC
Standby/
Alarm:
.082 mA
mA
mA
SD505-ADHR
SD505-DUCTR
(508 max.)
Aux. Pwr
Standby:
35 mA
2
mA
Alarm:
75 mA
2
mA
SLC
Standby/
Alarm:
.082 mA
mA
mA
SD505-DTS
SD505-DTS-K
(508 max.)
None, included with SD505-ADHR worst case.
SD505-ADH
SD505-DUCT
(508 max.)
None, included with detector current.
SLC Isolator Devices
SD500-LIM
(1024 max.)
Standby/Alarm
0.092 mA
mA
mA
SD505-6IB
(508 max.)
Accessories Modules
5815XL SLC Expander
(3 max.)
Standby/Alarm:
55 mA
mA
mA
5860 Remote Fire Alarm Annun.
(8 max.)
Standby:
20 mA
mA
Alarm:
25 mA
mA