IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide 
 
– 7 – 
Wiring the 659EN Line Fault Monitor (if required) 
The IPGSM-DPC is compatible with the Honeywell brand FACP’s listed on page 1 when the model 659EN 
Line Fault Monitor is installed. 
1.  Refer to the installation guide for the 659EN. 
2.  Mount the 659EN on the lower left side of the IPGSM-DPC cabinet. 
3.  DO NOT cut the 659EN’s BLACK Output Relay Jumper or the BLUE Voltage Trip Threshold 
Jumper. 
4.  Complete the interface wiring as shown below: 
 
to Dialer Capture Module, Terminal, Tip 2
to Dialer Capture Module, Terminal, Ring 2
to Power Boost 1, Terminal, OUTPUT 1, DC+
to Power Boost 1, Terminal, OUTPUT 1, DC-
to Power Boost 1, Terminal, ERTH GND
Wire to a
Zone on the Fire Panel
659EN
YEL
ORG
RED
BLK
GRN
IPGSM-DPC-013-
V
0
4.7K, 1/2 watt
IPGSM-DPC
 
 
 
       Example wiring for an addressable fire control panel: 
 
T11
T10
T9
T8
T7
T6
T1
T2
T3
T4
T5
1 0
2
3
4
5 6
7 8 9
10
11
12
13
14
15
1 0
2
3
4
5 6
7 8 9
TENS
ONES
LOOP
ADDRESS
TOP
B+  A+  B-  A-   A    B 
NO  NC    C 
TB2
TB5
SLC Loop
FIRE LITE Addressable Fire Alarm Control Panel
MS-9050UD
MMF-300A
Monitor Module
- To next device
+ on SLC Loop
Braided-shield/Drain
Wire
RELAY 1
ALARM CONTACTS
IPGSM-DPC
Commercial Fire Communicator
to Dialer Capture Module, Terminal, Tip 2
to Dialer Capture Module, Terminal, Ring 2
to Power Boost 1, Terminal, OUTPUT 1, DC+
to Power Boost 1, Terminal, OUTPUT 1, DC-
to Power Boost 1, Terminal, ERTH GND
659EN
YEL
ORG
RED
BLK
GRN
4.7K, 1/2 watt
B+
B-
Shield
IPGSM-DPC-014-V0