Emerson Model 1700 用户手册

下载
页码 350
Options for Frequency Output Fault Action
Options for Frequency Output Fault Action
Table 6-7:   
Label
Frequency output behavior
Upscale
Goes to configured Upscale value:
Range: 10 Hz to 15000 Hz
Default: 15000 Hz
Downscale
0 Hz
Internal Zero
0 Hz
None
 (default)
Tracks data for the assigned process variable; no fault action
CAUTION!
If you set mA Output Fault Action or Frequency Output Fault Action to None, be sure to set Digital
Communications Fault Action
 to None. If you do not, the output will not report actual process data,
and this may result in measurement errors or unintended consequences for your process.
Restriction
If you set Digital Communications Fault Action to NAN, you cannot set mA Output Fault Action or Frequency
Output Fault Action
 to None. If you try to do this, the transmitter will not accept the configuration.
6.4
Configure the discrete output
The discrete output is used to report specific flowmeter or process conditions. The discrete
output parameters control which condition is reported and how it is reported. Your
transmitter may have zero or one discrete output: Channel B can be configured as a
frequency output or a discrete output.
The discrete output parameters include:
Discrete Output Source
Discrete Output Polarity
Discrete Output Fault Action
Restriction
Before you can configure the discrete output, you must configure a channel to operate as a discrete
output.
Important
Whenever you change a discrete output parameter, verify all other discrete output parameters
before returning the flowmeter to service. In some situations, the transmitter automatically loads a
set of stored values, and these values may not be appropriate for your application.
Integrate the meter with the control system
Configuration and Use Manual 
93