Model IFT9701 Transmitter Instruction Manual
21
Power Supply and Output Wiring
 continued
Ge
tti
n
g
 Sta
rted
P
o
wer
 Su
pp
ly
 an
d O
u
tp
ut Wi
ri
ng
Mounting the 
Remo
te T
ransmitter
Be
fo
re
 Y
o
Begin
4.4
Connect output wiring
Figure 4-2 shows the milliamp and pulse output terminals.
Install twisted-pair, shielded cable, consisting of 20 AWG (0,5 mm²) to 16 AWG (1,5 mm²) 
wire.
For basic information on milliamp output wiring, see Section 4.4.1.
For instructions on connecting the milliamp output to a Bell 202 multidrop network, see 
Section 4.4.2.
For instructions on connecting a HART device to the milliamp output, see Section 4.4.3.
For instructions on pulse output wiring, see Section 4.4.4.
Figure 4-2
Output wiring terminals
Table 4-1
Wire guidelines for DC power supply
Wire size
Wire length
16 AWG (1,5 mm²) 
1500 feet (450 meters)
18 AWG (0,75 mm²)
1000 feet (300 meters)
20 AWG (0,5 mm²)
600 feet (200 meters)
• Terminate output cable shielding at gland or conduit fitting.
• 360° termination of shielding is not necessary.
• Do not terminate shield inside wiring compartment.
• The pull-up resistor must be of sufficient value to limit the total loop current to less 
than 500 ohms. Refer to Section 4.4.4 to determine the pull-up resistor needed.
Field wiring 
compartment
Sensor wiring 
compartment
Case ground
Active milliamp output
Internally powered
Passive pulse output
Requires pull-up resistor 
to external 5–30 VDC 
power supply
Conduit opening 
for output wiring