SMV 3000 Transmitter User’s Manual
1/99
164
A.6
Operation Notes
Generic Operations
Most operator actions initiated through Detail displays at the Universal
Station are generic for all Smartline transmitters. Refer to Section 7 in the
PM/APM Smartline Transmitter Integration Manual for details about
these generic operations.
This section outlines some differences in operations that are unique to the
multivariable STIMV IOP and the SMV 3000 transmitter in particular.
Detail Display
Difference
Page 2 of the Detail display for a multivariable STIM point includes an
additional field in the lower right hand corner for PV Number and Number
of PVs identification as shown in Figure A-6. This lets you quickly
identify what PV number you are viewing and how many PVs are
associated with this given SMV 3000 transmitter.
Figure A-6
Detail Display with PV Number and Number of PVs Field.
F101
SMV SLOT 1 - DIFF PRESS  03 UNIT 01
 
CONFIG PAGE
PVFORMAT        01
PVSRCOPT       ALL
PVCLAMP
CLAMP
PVALDR         ONE
PVALDEBEU   2.0000
INPTDIR    REVERSE
LOCUTOFF   -------
_________________ CONFIGURATION DATA ________________
PVCHAR   LINEAR
SENSRTYP SPT_DP
PIUOTDCF    OFF
BADPVPR     LOW
PVHHPR NOACTION
PVHIPR NOACTION
PVLLPR NOACTION
PVLOPR   NOACTION
PVROCPPR NOACTION
PVROCNPR NOACTION
______________ SMART TRANSMITTER DATA ______________
STITAG     FT3011
SENSRTYP   SPT_DP
PVCHAR     LINEAR
CJTACT        OFF
PIUOTDCF      OFF
DECONF   Pv_Sv_Db
PVRAW    50.000
URL     400.000
URV     250.000
LRV     0.00000
LUL     0.00000
STI_EU    INH2O
SECVAR    21.5762
DAMPING   0.00000
SERIALNO 10775120
STISWVER      2.5
STATE          OK
COMMAND      NONE
TRANSMITTER SCRATCH PAD:
TRANSMITTER STATUS     :
1 OF 1
23 Jun 98 11:15:23  6
PV Number
Number of PVs
Database Mismatch
Parameters
The following parameters are added to the list of parameters that the
STIMV IOP checks for database mismatches between itself and the
transmitter.
• PV Number
• Number of PVs
Continued on next page