Omega Engineering M-4066 用户手册

下载
页码 63
OMWT-SOFT-OPC Server
OMWT-SOFT-OPC Server .ini File Format x 17
Logging
[Logging] - section name
LogRate - 0: no logging; 1-100000 logging interval in seconds.  5 sec or 
greater OMWT-SOFT-OPC opens and closes the log file at every 
logging interval.  Less than 5 OMWT-SOFT-OPC leaves the file open 
until OMWT-SOFT-OPC is terminated or “Server.Logging.LogRate” is 
set to 0 or 5 and greater.
LogFile - full pathname for the log file - default "OMWT-SOFT-
OPC.LOG"
OfflineIndicator - character or string to indicate offline - NULL: last value
LogErrors - 1 - log runtime network errors to OMWT-SOFT-OPC.ERR.  0 
- do not log errors
IP Addresses
[IP Addresses] – section name (for OMWT-RECIP receivers)
IPWaitPort – port number that OWMT-SOFT-OPC will wait for 
connections initiated by an IP receiver.  (default is 1060)
ForwardPort – port number that OWMT-SOFT-OPC will wait for 
connections to forward received packets.  (default is 0 which means 
disabled)  OWMT-SOFT-OPC will forward received packets through 
this connection.  Each packet has the following format: sensor 
packet,node number, node description, sensor label.  The INI 
parameter FowardAll in the [Server] section controls what packets get 
sent.
DIGITAL I/O 
[Devicen] - Section name.
Address – serial number of the sensor.
DeviceType - Device type. (DeviceType=DIGITAL)
PollTime - How often to poll the device. (ms)
Label - Name used for the device (and Topic).
Log - Enable/disable logging of device.
OutputOnDemand - Output is initiated on demand or during poll.
DescriptionA - General purpose description.
DescriptionB - General purpose description.