OMWT-SOFT-OPC Server
OMWT-SOFT-OPC Server .ini File Format x 27
Wireless Analog Output
(OMWT-ANGOUT)
[Devicen] - Section name.
Address - serial number of the sensor.
NodalAddress – node where the output will be sent.  Defaults to 0 for the 
OMWT-REC323-600 Receiver.   For OMWT-RECIP, the node number 
represents each receiver starting at 1.  If set to 0, OMWT-SOFT-OPC 
will send the output packet to all nodes.
DeviceType - Device type. (DeviceType= OUTPUTANALOG)
PollTime - How often to poll the device or wait for packet. (ms)  Defaults to 
0 for outputs.
Label - Name used for the device (and Topic) (typically 
OUTPUTANALOG1).
Log - Enable/disable logging of device.
LogDecimalPlaces - Number of decimals to create when logging.
Description - General purpose description.
Cal1Raw - Two point calibration point 1 (default 0).
Cal2Raw - Two point calibration point 2 (default 4095).
Cal1Engr - Two point calibration engineering units for point 1 (default 0).
Cal2Engr - Two point calibration engineering units for point 2 (default 
100).
Units - units label (default "%").
Description - Generic description field
OutTries – number of times to send the output packet.  (default 10)
OutInterval – (in milliseconds) – the interval of time between sending 
output packets.  (default 1000).