Raypak 992B-2342B 产品宣传页

下载
页码 2
Catalog No.:  2000.312D 
Effective:  11-15-07 
Replaces:  1-1-07 
Hi Delta – Type H 
Models 992B-2342B 
Model            
 
 
 
 
SPECIFICATIONS 
 
 
 
 
Approx. 
 MBTUH 
Firing
A
H
K
T
W
Amp. Shipping 
Model Input Output 
Stages
Width  NPT
   
 
Draw* Wt. (Lbs.) 
992B 990  832 
3
57-1/8
2-1/2 10 10 16-13/16
<12
900
1262B 1260  1058 
68-1/2
2-1/2 12 10
20-9/16 
<12 1010 
1532B 1530  1285 
79-7/8
2-1/2 12 10
24-3/8 
<12 1225 
1802B 1800  1512 
91-1/8
2-1/2 14 10
28-1/8 
<12 1350 
2002B 1999  1679 
4  102-1/2 2-1/2 14 10 31-15/16
<12 1450 
2072B 2070  1739 
4  102-1/2 2-1/2 14 10 31-15/16
<12 1450 
2342B 2340  1966 
4  113-7/8 2-1/2 16 10 35-11/16
<12 1520 
Dimensions are in inches. 
* Without pump 
RATES OF FLOW AND PRESSURE DROPS 
 
20°F 
T
30°F 
T
Min. Flow 
Max. Flow
Model GPM
P (ft) GPM P (ft) GPM  P (ft)  T  GPM P (ft) T
992B
84
5.6
56
2.5
42 1.5 40 
132
14.0
13
1262B
107 10.0  71 
4.5 53 2.6 40 
132 
15.5 
16
1532B
130 
16.0 
86 
7.1 65 4.1 40 
132 
16.5 
20
1802B
N/A N/A 102 
10.8 76  6.0 40 132 18.0 23
2002B
N/A N/A 113 
14.0 85  8.1 40 132 19.5 26
2072B
N/A N/A 117 
15.0 88  8.7 40 132 19.5 27
2342B
N/A N/A 132 
21.0 99 12.0 40 132 21.0 30
Basis is 30 GPM or 40°F 
∆T for minimum flow, 132 GPM for maximum flow. 
NOTE:  Pump location 
varies based on model 
and application 
NOTES:  1.  Rates shown are for natural or propane gas, and elevations up to 5,000 feet. For installation above 5,000 feet, please contact manufacturer. 
 
2.  Required natural gas pressure is 7 – 10.5” WC. Required propane gas pressure is 11 - 13” WC.
 
Raypak, Inc.  