Project Name / Date 
 
Division 23 52 33.13 - 2
 
2.2 WATER 
HEATERS 
A. General 
1.  The water heater(s) shall be fired with              gas at a rated input of    
  
 BTU/hr. 
2.  The water heater(s) shall be CSA tested and certified with a minimum thermal efficiency of 85 
percent at full fire. 
3.  The water heater(s) shall be ASME inspected and stamped and National Board registered for 
160 PSIG working pressure, complete with a Manufacturer's Data Report. 
4.  The water heater(s) shall have a floor loading of 65 lbs. /square foot or less. 
B. Heat 
Exchanger 
1.  The heat exchanger shall be of a single-bank, horizontal-grid design with twelve integral 
copper fin tubes, each end of which is rolled into an ASME water heater quality steel tube 
sheet. 
2.  The heat exchanger shall be sealed to 160 PSIG rated bronze headers with silicone "O" rings, 
having a temperature rating over 500°F. 
3.  The low water volume heat exchanger shall be explosion-proof on the water side and shall 
carry a twenty-year warranty against thermal shock. 
4.  The headers shall be secured to the tube sheet by stud bolts with flange nuts to permit 
inspection and maintenance without removal of external piping connections. The heat 
exchanger shall incorporate "V” baffles between the tubes to ensure complete contact of the 
external tube surfaces with the products of combustion. 
5.  The water heater(s) shall be capable of operating at inlet water temperatures as low as 105°F 
without condensation. 
6.  The water heater(s) shall be designed to accommodate field changes of either left or right 
hand plumbing and electrical while leaving the tube bundle in place. 
C. Burners 
1.  The tubular burners shall have multiport radial gas orifices, punched ports and slots, be 
capable of quiet ignition and extinction without flashback at the orifice, and be manufactured 
from corrosion-resistant, titanium-stabilized stainless steel with low expansion coefficient. 
2.  The burners will be supplied with a fan-assisted, clean burning, and highly efficient fuel-air 
mixture. 
D. Pilot 
Control 
System 
1.  The water heater(s) shall be equipped with a 100 percent safety shutdown system. 
2.  The ignition shall be Hot Surface Ignition type with full flame rectification by remote sensing 
separate from the ignition source, with a three-try-for-ignition sequence, to ensure consistent 
operation. 
3.  The igniter will be located away from the water inlet to protect the device from condensation 
during startup. 
4.  The ignition control module shall include an LED that indicates six (6) individual diagnostic 
flash codes. 
5.  Two external viewing ports shall be provided, permitting visual observation of burner 
operation. 
E. Gas 
Train 
1.  The water heater(s) shall have a firing/leak test valve and pressure test valve as required by 
CSD-1. 
2.  The water heater(s) shall have dual-seated main gas valve(s). 
3.  Gas control trains shall have a redundant safety shut-off feature, main gas regulator, shut-off 
cock and plugged pressure tapping to meet the requirements of ANSI Z21.10.3/CSA 4.3. 
F.  Water Heater Control 
1.  The following safety controls shall be provided: 
a.  High limit control 
b.  Flow switch, mounted and wired 
c.  ____PSIG ASME pressure relief valve, piped by the installer to an approved drain 
d.  Temperature and pressure gauge