Rinnai RV53I 用户手册

下载
页码 60
 
24 
RV53i & RV53e Operation and Installation Manual 
  Venting 
Instructions 
(RV53i) 
     
 
 
 
 
 
 
 
 
 
•  This water heater is a direct vent water heater and 
therefore is certified and listed with the vent 
system.  You must use vent components that are 
certified and listed with the water heater model. 
•  Do not combine vent components from different 
manufacturers. 
•  The vent system must vent directly to the outside 
of the building and use outside air for combustion. 
•  Venting should be as direct as possible with a 
minimum number of pipe fittings. 
•  Avoid dips or sags in horizontal vent runs by 
installing supports per the vent manufacturer’s 
instructions. 
•  Support horizontal vent runs every four feet and all 
vertical vent runs every six feet or in accordance 
with local codes. 
•  Vent diameter must not be reduced. 
•  Do not connect the venting system with an existing 
vent or chimney. 
•  Do not common vent with the vent pipe of any 
other water heater or appliance. 
•  Vent connections must be firmly pressed together 
so that the gaskets form an air tight seal. 
•  The vent piece connected to the water heater must 
be secured with one self-tapping screw. 
•  Refer to the instructions of the vent system 
manufacturer for component assembly instructions. 
•  If the vent system is to be enclosed, it is suggested 
that the design of the enclosure shall permit 
inspection of the vent system.  The design of such 
enclosure shall be deemed acceptable by the 
installer or the local inspector. 
Condensate  
Condensate formation can occur in high efficiency 
direct vent appliances.  To prevent condensate 
damage follow these instructions. 
Intake / Exhaust Guidelines 
Refer to the specific instructions on your vent product for additional 
installation requirements. 
NOTICE 
Provisions must be made to prevent the condensate 
from entering the water heater.  Without proper 
drainage or disposal, condensate will damage the heat 
exchanger. 
     WARNING 
The condensate trap must be primed before operation 
to prevent exhaust gases from entering the building. 
 
NOTICE 
If it becomes necessary to access an enclosed vent 
system for service or repairs, Rinnai is not responsible 
for any costs or difficulties in accessing the vent 
system.  Warranty does not cover obtaining access to 
an enclosed vent system. 
•  Vertical terminations must incorporate a 
condensate drain and trap as close as possible to 
the appliance. 
•  The RV53i water heater has an integrated 
condensate collector. 
•  Rinnai offers a condensate trap.   
•  Regions of cold climate will create more 
condensate in the vent system.  The condensate 
collector should be used in cold climates. 
•  Use only vent that is approved and identified as 
acceptable for your particular model. 
•  Do not use PVC, CPVC, ABS or galvanized 
material to vent this appliance. 
•  Slope the venting toward the appliance according to 
the vent manufacturers installation instructions. 
•  All condensate must drain and be disposed of per 
local codes. 
•  Use only PVC or CPVC pipe for the condensate 
drain line.   
•  The condensate drain pipe should be as short as 
possible and have a downward pitch. 
•  Do not connect the condensate drain pipe directly 
to the rain sewer. 
•  The condensate drain pipe (along its entire length) 
must be at least the same diameter as the drain 
line. 
•  The end of the condensate drain pipe should be 
open to the atmosphere.  The end should not be 
under water or other substances. 
•  Do not connect the condensate drain line with an 
air conditioning evaporator coil drain. 
•  To minimize freezing of the condensate, run the 
condensate drain line through an interior wall or 
between insulation and an interior wall. 
•  The condensate collector should be used for all 
hydronic heating applications.