GAS PRESSURE SETTING 
 
 
The working gas pressure on the water heater is electronically controlled and factory set.  
Under normal circumstances it does not require adjustment during installation. Perform 
this procedure only if the unit is not operating correctly and all other possible causes for 
incorrect operation have been eliminated.  
Contact Rinnai UK before 
attempting to alter the gas pressure.  Failure to do so could void 
the warranty.
 
 
 
1. Turn 'OFF' the gas supply. 
 
2.  Turn 'OFF' 230V power supply. 
 
3.  Remove the front cover from the appliance. 
 
4.  Check gas type switches no.1 and no. 2 of 
SW2 (fig. 1) are in the correct position for the 
type of gas (Nat. or LPG) you are using. 
(SW2 is top set of switches.) 
 
 
 
 
 
 
 
 
 
5.  Attach pressure gauge to burner test point.  
(fig. 2) 
 
6.  Turn 'ON' the gas supply. 
 
7.  Turn 'ON' 230V power supply. 
 
8. If remote controllers are fitted, turn the unit 
'ON' at the master controller, select a 
maximum delivery  temperature and open a 
hot water tap  fully. (CAUTION: Ensure 
building occupants do not have access to 
hot water outlets during this procedure.) 
 
9.  Set the appliance to 'Forced Low' combustion 
by setting No. 2 dipswitch of the bottom set of 
dip switches (SW3)  to 'ON'. (fig 3) 
 
10.Check the burner test point operating 
pressure. 
 
test pt. screw 
fig.1
fig.1
fig.2
fig.3
ON
N.G.
1
2
O
F
F
ON
SW2
SW2
SW3
Prop.G
1
2
2
3
O
F
F
O
F
F
ON
SW2
SW3