VA Series Indoor LS Manual 
Pipe Sizing Procedure - Example 
1.  Determine the cubic feet per hour of gas required by dividing the gas input (on the rating plate) by the heating 
value of the gas (available from the local gas company).  The gas input needs to include all gas products at 
the location and the maximum BTU usage at full load when all gas products are in use.  
 
       Gas 
Input 
of 
Rinnai 
water 
heater 
(BTU 
HR) 
Cubic Feet per Hour (CFH) =  
         Heating 
Value 
of 
Gas 
(BTU 
FT 
2.  Use the table for your gas type to find the pipe size required for your cubic feet per hour of gas and your pipe 
length. 
Example:  The heating value of propane gas for your location is 2516 BTU / FT 
3
.  The gas input of the R94LSi is 
190,000 BTU/HR.   Additional appliances at the location require 75,000 BTU/HR. 
 
Therefore the cubic feet per hour = (190,000+75,000) / 2516 = 105.3 FT 
3
/ HR. 
 
If the pipe length is 100 ft then the 3/4 inch pipe size capable of supplying 197 FT 
3
/ HR of propane gas 
will be adequate. 
Pipe Sizing Table - Natural Gas 
Pipe Sizing Table - Propane Gas 
Pipe Size (inches) 
3/4 
1 1/4 
1 1/2 
10 
273 514 1060 
1580 
20 
188 353 726 1090 
30 
151 284 583 873 
40 
129 243 499 747 
50 
114 215 442 662 
60 
104 195 400 600 
70 
95 179 368 552 
80 
89 167 343 514 
90 
83 157 322 482 
100 
79 148 304 455 
125 
70 131 269 403 
150 
63 119 244 366 
175 
58 109 224 336 
200 
54 102 209 313 
Length  
Length  
Pipe Size (inches) 
1/2 3/4  1 1 
1/4 
10 
291 608 1150 
2350 
20 
200 418 787 1620 
30 
160 336 632 1300 
40 
137 287 541 1110 
50 
122 255 480 985 
60 
110 231 434 892 
80 
101 212 400 821 
100 
94 197 372 763 
125 
89 185 349 716 
150 
84 175 330 677 
175 
74 155 292 600 
200 
67 140 265 543 
Inlet Pressure:  less than 2 psi (55 inches W.C.) 
Pressure Drop:  0.3 inches W.C. 
Specific Gravity: 0.60 
Inlet Pressure:  11.0 inches W.C. 
Pressure Drop:  0.5 inches W.C. 
Specific Gravity: 1.50 
Schedule 40 Metallic Pipe 
cubic feet per hour 
Schedule 40 Metallic Pipe 
cubic feet per hour 
  Gas Piping   
 
 
 
 
 
 
 
                       
The gas supply must be capable of handling the entire gas load at the location.  Gas line sizing is based on gas 
type, the pressure drop in the system, the gas pressure supplied, and gas line type.  Refer to the National Fuel 
Gas Code, NFPA 54
, for proper gas line sizing.  The below information is provided as an example.