Rinnai RC80E 用户手册

下载
页码 64
 
 
Manual - Rinnai Condensing Water Heaters 
27 
  Flue Terminal Clearances (
ANS 
Z21.10.3, 
CSA 
4.3)         
 
    INSIDE
CORNER DETAIL
FIXED
CLOSED
OPERABLE
FIXED
CLOSED
OPERABLE
B
B
B
A
J
B
M
C
F
B
B
E
D
L
G
A
H
K
I
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves 
both dwellings. 
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. 
∗ 
For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearances are in accordance with local installation codes and the 
requirements of the gas supplier. 
 
Clearance to opposite wall is 24 inches (60 cm) for Canada and US. 
X
V
AIR SUPPLY INLET 
 
VENT TERMINAL 
 
AREA WHERE 
TERMINAL IS NOT 
PERMITTTED 
Ref 
Description 
Canadian Installations 
US Installations 
Clearance above grade, veranda, porch, deck, or balcony 
12 inches (30 cm) 
12 inches (30 cm) 
Clearance to window or door that may be opened 
36 inches (91 cm) 
12 inches (30 cm) 
Clearance to permanently closed window 
Vertical clearance to ventilated soffit, located above the terminal 
within a horizontal distance of 2 feet (61 cm) from the center line 
of the terminal 
* * 
Clearance to unventilated soffit 
Clearance to outside corner 
Clearance to inside corner 
Clearance to each side of center line extended above meter/
regulator assembly 
3 feet (91 cm) within a height 
15 feet (4.5 m) above the 
meter/regulator assembly 
Clearance to service regulator vent outlet 
36 inches (91 cm) 
Clearance to nonmechanical air supply inlet to building or the 
combustion air inlet to any other appliance 
36 inches (91 cm) 
12 inches (30 cm) 
Clearance to a mechanical air supply inlet 
6 feet (1.83 m) 
3 feet (91 cm) above if within 
10 feet (3 m) horizontally 
Clearance above paved sidewalk or paved driveway located on 
public property 
7 feet (2.13 m) 1 * 
Clearance under veranda, porch, deck, or balcony  
12 inches (30 cm) 2