Rinnai RC98I 用户手册

下载
页码 64
 
 
Manual - Rinnai Condensing Water Heaters 
37 
  Space 
Heating 
       
 
 
 
 
 
 
 
 
 
 
 
 
If the water heater is to be used for both water (potable) heating and space heating then the following apply. 
•  The piping and components connected to the water heater shall be suitable for use with potable water. 
•  Toxic chemicals, such as used for boiler treatment, shall not be introduced into the potable water. 
•  The water heater shall not be connected to any heating system or components previously used with a 
nonpotable water heating appliance. 
•  When the system requires water for space heating at temperatures higher than required for other uses, a 
means such as a mixing valve shall be installed to temper the water for other uses in order to reduce the 
scald hazard potential. 
Temperature Setting 
When using this appliance to provide domestic hot water it is recommended that the domestic hot water 
temperature be reduced to acceptable temperatures in accordance with local codes.  In the absence of local 
codes it is recommended that the domestic hot water temperature be set to 140º F (60º C) or lower in accordance 
with UPC 501.6 by using mixing valves or the temperature controller for the water heater. 
Pumps 
Only use pumps of brass or stainless steel construction.  Do not use pumps of iron construction as they will 
oxidize and clog the inlet filter on the appliance. 
Pumps circulating water through the water heater must be sized to overcome the pressure loss through the water 
heater, the heating system, and any additional plumbing pressure losses.  The pressure drop curve based on the 
water heater model is provided in this manual. 
Replacement 
When replacing an existing space heating application’s water heating source (boiler, tank water heater, tankless 
water heater, etc.) with Rinnai water heaters, ensure that the water heaters are sized to adequately provide the 
necessary BTU input for the desired space heating application.  Rinnai water heaters are designed to maintain a 
constant outlet temperature and will supply only the necessary amount of BTU’s to maintain that temperature.  
Depending on the application the maximum BTU rating of the unit may not be achieved.  Contact Rinnai’s 
Applications Engineering Department for assistance at (800) 621-9419 ext. 4490. 
Iron Components 
Do not use Rinnai water heaters directly for space heating applications involving iron radiators or applications with 
any iron components.  Iron components may oxidize creating rust that will clog the inlet filter of the Rinnai water 
heater. 
 
Space heating applications are considered commercial applications for warranty purposes.