Figure 4
 
Direct Vent Terminal Clearances 
 
 
 
Canadian Installations1 
US Installations2 
A= 
Clearance above grade, veranda, porch, deck or 
balcony 
12 inches (30 m) 
12 inches (30 cm) 
B= 
Clearance to widow or door that may be opened 
12 inches (30 m) 
9 inches (23 cm) for 
appliances > 10,000 Btuh 
(3 kW) and ≤ 50,000 
Btuh (15 kW), 12 inches 
(30 cm) for appliances > 
50,000 Btuh (15 kW) 
C= 
Clearance to permanently closed widow 
*b 
*b 
D= 
Vertical clearance to ventilated soffit located above the 
terminal within a horizontal distance of 2 feet (61 cm) 
from the center line of the terminal 
12 inches (30 cm) *a 
 12 inches (30 cm) *a 
E= 
Clearance to unventilated soffit 
12 inches (30 cm) *a 
12 inches (30 cm) *a 
F= 
Clearance to outside corner 
*b 
*b 
G= 
Clearance to inside corner 
*b 
*b 
H= 
Clearance to each side of center line extended above 
meter/regulator assembly 
3 feet (91 cm) within a 
height 15 feet (4.6 m) 
above the 
meter/regulator 
assembly 
*b 
I= 
Clearance to service regulator vent outlet or oil tank 
vent 
36 inches (91 cm) 
*b 
J= 
Clearance to non-mechanical air supply inlet to building 
or the combustion air inlet to any other appliance 
12 inches (30 cm) 
9 inches (23 cm) for 
appliances > 10,000 Btuh 
(3 kW) and ≤ 50,000 
Btuh (15 kW), 12 inches 
(30 cm) for appliances > 
50,000 Btuh (15 kW) 
K= 
Clearance to a mechanical air supply inlet 
6 feet (1.83 m) 
3 feet (91 cm) above if 
within 10 feet horizontally 
L= 
Clearance above paved sidewalk or paved driveway 
located on public property 
7 feet (2.13 m)† 
*b 
M= 
Clearance under a veranda, porch, deck, or balcony 
12 inches (30 cm) ‡ 
*b