Water Connections continued- 
     
 
WARNING 
For protection against excessive temperatures and pressure, install 
temperature and pressure protective equipment required by local codes, 
but not less than a combination temperature and pressure relief valve 
certified by a nationally recognized testing laboratory that maintains 
periodic inspection of production of listed equipment or materials as 
meeting the requirements of the Standard for Relief Valves and 
Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI 
Z21.22
 and the Standard CAN1-4.4 Temperature, Pressure, 
Temperature and Pressure Relief Valves and Vacuum Relief Valves
.  
The combination temperature and pressure relief valve must be marked 
with a maximum set pressure not to exceed the maximum working 
pressure of the water heater.  The hourly BTU discharge capacity or the 
rated steam relief capacity of the combination temperature and pressure 
relief valve must not be less than the input rating of the water heater. 
Install the combination temperature and pressure relief valve into the 
opening provided and marked for this purpose on the water heater.  
Note:  Some models may already be equipped or supplied with a 
combination temperature and pressure relief valve.  Verify that the 
combination temperature and pressure relief valve complies with local 
codes.  If the combination temperature and pressure relief valve does 
not comply with local codes, replace it with one that does.  Follow the 
installation instructions above on this page. 
Install a discharge line that terminates six (6) inches (15 cm) above the 
floor, or any distance below the structural floor, to the outlet of the 
combination temperature and pressure relief valve.  DO NOT allow 
water from the discharge line to contact any live electrical part.  The 
discharge line is to be installed to allow for complete drainage of both 
the combination temperature and pressure relief valve and the discharge 
line.  The water from the discharge line must be directed to a suitable 
drain or area that will not be damaged by water Refer to “LOCATING 
THE WATER HEATER.”  The discharge opening must not be subjected 
to blockage or freezing.  DO NOT thread, plug or cap the discharge line. 
It is recommended that a minimum clearance of four (4) inches (10.2 
cm)
 be provided on the side of the water heater for servicing and 
maintenance of the combination temperature and pressure relief valve. 
 
Do not place a shutoff valve between the combination temperature and 
pressure relief valve and the water heater, or on discharge pipes 
between such valves or the atmosphere.