Kenmore 153.31604 用户手册

下载
页码 24
12
Wiring 
You must provide all wiring of the proper size outside of the 
water heater. You must obey local codes and electric company 
requirements when you install this wiring.
If you are not familiar with electric codes and practices, or if 
you have any doubt, even the slightest doubt, in your ability 
to connect the wiring to this water heater, obtain the service 
of a competent electrician. Contact your Sears salesperson 
to arrange for a professional electrician.
WIRING DIAGRAMS
 
C-2 
C-2
 
STANDARD WIRING FOR 
STANDARD WIRING FOR
 
SINGLE ELEMENT 240 VOLT 
SINGLE ELEMENT 120 VOLT
FIGURE 11.
WATER HEATERS EQUIPPED FOR ONE VOLTAGE ONLY: 
This  water  heater  is  equipped  for  one  type  voltage  only. 
Check  the  rating  plate  near  the  bottom  access  panel  for 
the  correct  voltage.  DO  NOT  use  this  water  heater  with 
any voltage other than the one shown on the model rating 
plate. Failure to use the correct voltage can cause problems 
which can result in DEATH, SERIOUS BODILY INJURY, OR 
PROPERTY DAMAGE. If you have any questions or doubts 
consult your electric company.
If  wiring  from  your  fuse  box  or  circuit  breaker  box  was 
aluminum for your old water heater, replace it with copper 
wire. If you wish to reuse the existing aluminum wire, have 
the  connection  at  the  water  heater  made  by  a  competent 
electrician. Contact your Sears salesperson to arrange for 
a professional electrician.      
1.  Provide a way to easily shut off the electric power when 
working on the water heater. This could be with a circuit 
breaker or fuse block in the entrance box or a separate 
disconnect switch.
2.  Install and connect a circuit directly from the main fuse or 
circuit breaker box. This circuit must be the right size and 
have its own fuse or circuit breaker. Refer to the chart in 
the  “Product  Specifications”  section  for  the  correct  size 
wire and fuse or circuit breaker.
3.  If metal conduit is used for the grounding conductor:
A.  The  grounding  electrode  conductor  shall  be  of  copper, 
aluminum, or copperclad aluminum. The material shall be 
of one continuous length without a splice or joint.
B.  Rigid  metal  conduit,  intermediate  metal  conduit,  or  
electrical metallic tubing may be used for the grounding  
means if conduit or tubing is terminated in fittings approved 
for grounding.
C.  Flexible metal conduit or flexible metallic tubing shall be 
permitted for grounding if all the following conditions are 
met:
•  The length in any ground return path does not exceed 6 
feet.
•  The circuit conductors contained therein are protected by 
overcurrent devices rated at 20 amperes or less.
•  The conduit or tubing is terminated in fittings approved for 
grounding.
For complete grounding details and all allowable exceptions, 
refer to the current edition of the NEC - National Electrical 
Code NFPA 70.
4.  A  standard  1/2”  conduit  opening  has  been  made  in  the 
water heater junction box for the conduit connection.
5.  Use wire nuts and connect the power supply wiring to the 
wires inside the water heater’s junction box.
6.  The water heater must be electrically “grounded” by the 
installer. A green ground screw has been provided on the 
water heater’s junction box. Connect ground wire to this 
location.
7.  Replace  the  wiring  junction  cover  using  the  screw 
provided.
WIRING CONNECTIONS
FIGURE 12.