T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
7
63-4355—4
Fig. 9. Mounting subbase or wallplate.
WIRING SUBBASE/WALLPLATE
IMPORTANT
All wiring must comply with local electrical codes 
and ordinances.
Follow equipment manufacturer wiring instructions when 
available. Refer to the Wiring section for typical hookups. 
A letter code is located near each terminal for identification. 
Refer to Table 6 for terminal designations.
CAUTION
Electrical Shock Hazard.
Power supply can cause electrical shock.
Disconnect power before beginning installation.
1.
Loosen the terminal screws on the subbase/wallplate 
and connect the system wires. See Fig. 10.
IMPORTANT
Use 18-gauge, solid-conductor color-coded 
thermostat cable for proper wiring. If using 18- gauge 
stranded wire, no more than ten wires can be used. 
Do not use larger than 18-gauge wire.
2.
Securely tighten each terminal screw. 
3.
Push excess wire back into the hole.
4.
Plug the hole with nonflammable insulation to prevent 
drafts from affecting the thermostat.
Fig. 10. Proper wiring technique.
WIRES 
THROUGH WALL
WALL
WALL
ANCHORS
(2)
M10237
LEDS
MOUNTING 
HOLES
MOUNTING 
SCREWS
M4826
FOR WRAPAROUND 
INSERTION STRIP 
7/16 IN. (11 MM).
FOR STRAIGHT INSERTION 
STRIP 5/16 IN. (8 MM).
Table 6. Terminal Designations and Descriptions.
Terminal Designations
Typical Connection
Function
Terminal 
Type
Standard
Alternate
A1
A2
a
Dry auxiliary contacts for economizer control; A1 is normally open 
during Unoccupied periods and closed during Occupied periods.
Output
Dry contact
A1, A2
Damper control relay (Q7300L only).
Input, Output 24V powered 
contact
A2
A1
a
Dry auxiliary contacts for economizer control (A2 is common).
Input
Dry contact
A3
Dry auxiliary contacts for economizer control; A3 is normally open 
during Occupied periods and closed during Unoccupied periods.
Output
Dry contact
AS, AS
C7150B Discharge Air Sensor connection.
Input
B
Heating changeover valve.
Output
24V powered 
contact
C1, C2, C3, 
C4, C5
Communication input for T7147.
Input
Low power
E
K
Emergency heat relay.
Output
24V powered 
contact
a
Some OEM models reverse the economizer terminal designations A1 and A2.
b
Some OEM models label the terminal for transformer common B.
c
Applies only to Q7300H2037.