Honeywell T7984 C 用户手册

下载
页码 8
T7984 A,B,C ELECTRONIC MODULATING CONTROL THERMOSTATS 
SPECIFICATIONS 
IMPORTANT 
The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not 
exactly match the listed specifications. Also, this product is tested and calibrated under closely controlled conditions, 
and some minor differences in performance can be expected if those conditions are changed. 
MODELS: T7984A,B,C, 2 to 10 Vdc analog output 
Table 1. Model Specifications 
Model 
Output 1 
Cool/Heat
Changeover
For Output 1 
Output 2 
Night Setback 
Main 
Temperature 
Sensor * 
Mode Selection 
Input 
T7984A 
Modulating 2 to 
10 Vdc 
Dry Contact or 
Sensor 
On/off 
-
Internal or 
remote 
-
T7984B 
Modulating 2 to 
10 Vdc 
-
-
Dry Contact 
Internal or 
remote 
Jumper 
T7984C 
Modulating 2 to 
10 Vdc 
Dry Contact or 
Sensor 
Modulating 2 to 
10 Vdc 
Dry Contact 
Internal or 
remote 
-
* Remote sensor models are: 
272845 Remote wall mount sensor 
272847 Remote duct mount sensor 
DIMENSIONS 
See Figure 1. 
MOUNTING: Mounts to single-gang NEMA-standard 2"x 4" 
electrical box, or directly to wall requires 1 1/8“ [35„mm] 
access hole for wiring. 
WIRING: Four to eight 1/8“ screw terminals suitable for 2 no. 
18 AWG [1 mm 2] wires each depending on model. 
POWER SUPPLY: 19-30 Vac, 50-60 Hz, 2 VA, Class 2. (Does 
not include actuator or reheat stage power requirements.) 
OPERATING AMBIENT: 
32-104°F [0-40°C] at 5-95% Relative Humidity (non-
condensing). 
ACCURACY: 1°F (0.6°C) PRECISION: ±1°F (0.5°C) tempera-
ture after stabilization. 
PRECISION: ±1°F (0.5°C) temperature after stabilization. 
SETPOINT RANGE: 55-90°F [13-32°C], T7984A. 
Heating: 55-75°F [13-24°C], T7984B, C*. 
Cooling: 75-90°F [24-32°C], T7984B, C*.
ORDERING INFORMATION 
* The maximum heating setpoint and minimum cooling 
setpoint is electronically limited to 75°F [24°C]. 
REMOTE SENSOR: 47 kΩ NTC thermistor [part nos. 272845 
and 272847]. 
ANALOG OUTPUT: 2 to 10 Vdc, 2 mA max. 
SWITCHED OUTPUT RATING: 0.5A running, 1.1A inrush, 
24Vac, protected with selfresetting fuse. 
OPERATING PARAMETERS: See Table 2 for installer selections.
 APPROVALS: 
Designed for Class II low voltage installation only. 
Case and cover meets UL„94-5V flammability requirements, 
and North American codes for line voltage thermostat 
enclosures. 
Meets requirements of F.C.C. Part 15 Class B, IEC 801-3 for 
radio frequency interference. 
ACCESSORIES: 
272845 - Remote sensor (wall mounted). 
272846 - Adaptor plate for 2-gang NEMA, or British 75 mm 
electrical box.
 272847 - Remote sensor (duct mounted). 
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the 
TRADELINE® Catalog or price sheets for complete ordering number. 
If you have additional questions, need further information, or would like to comment on our products or services, please write or 
phone: 
1.   Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory). 
2.   Honeywell Customer Care  
1885 Douglas Drive North  
Minneapolis, Minnesota 55422-4386  
In Canada–Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.  
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, 
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.  
95C-10815–2