Honeywell V8944B 用户手册

下载
页码 12
V4943/V8943B,C,N; V4944/V8944B,C,L,N REGULATING DIAPHRAGM GAS VALVES
11
65-0214—08
Checkout
1. Valve outlet pressure measurements are made at a point 
approximately five pipe diameters downstream from the 
valve outlet. Consider pressure measurements made at 
the outlet pressure tap as reference measurements only, 
because turbulence and dynamic gas flow effects may 
result in erratic pressure readings. 
2. Shut off gas supply to valve and make sure valve is 
closed when setting up pressure measuring equipment. 
3. Set up pressure measuring equipment.
4. Make sure the valve is closed. Turn on the supply gas to 
the valve.
5. Set the thermostat or controller to energize the valve and 
check the final outlet pressure. See step 1. Allow enough 
time for the system pressure to stabilize.
6. For regulator setpoint and spring range, please refer to 
Table 3.
7. The low pressure regulator (V4944/V8944B,C,L,N) and 
high pressure regulator V4943V8943B,C,N and
 V4944/V8944B,C,L,N) adjustment screws (use a T-40 
six-lobe [TORX®] driver or 5/16-in. standard driver) are 
located under the slotted aluminum screw cap(s) of the 
adjustment screw housings (see Fig. 1). To adjust the 
pressure setting:
a. Temporarily remove the slotted aluminum screw cap 
and gasket from the housing that contains the 
regulator adjustment setscrew.
b. Turn the adjustment setscrew (use a T-40 six-lobe 
[TORX®] driver or 5/16-in. standard driver) clockwise 
to increase the pressure setting or counterclockwise 
to decrease the pressure setting. Allow adequate time 
(30 to 60 seconds) for the pressure to reach 
equilibrium between pressure adjustments.
c.  After the regulators have been properly adjusted, 
replace the gasket and slotted aluminum screw cap 
on the adjustment screw housing. 
8. Start the system and observe its operation through at 
least one complete cycle to make sure the valve 
functions properly.
Valve Leak Test (See Fig. 15).
This test checks the tightness closure of a gas safety shutoff 
valve. It should be performed by a qualified technician during 
the initial startup of a burner system, or whenever the valve is 
replaced (see Service Information section). It is recommended 
that this test also be included in scheduled inspection and 
maintenance procedures.
1. De-energize the control system to make sure there is no 
power to the safety shutoff valve (C) shown in Fig. 15.
2. Close the upstream manual gas cock (A).
3. Make sure the manual test petcock (F) is closed in the 
leak test tap assembly (D).
4. Remove the leak test tap plug (valve outlet pressure tap 
can be used as a test tap) and connect the test 
apparatus to the leak test tap (D).
5. Close the downstream manual gas cock (E).
6. Open the upstream manual gas cock (A).
7. Run the safety shutoff valve (C) to its fully open position 
(through the safety system); then immediately 
de-energize the system to close the valve.
8. Immerse a 1/4 in. tube vertically 1/2 in. (13 mm) into a jar 
of water.
9. Slowly open the test petcock (F).
10. When the rate of bubbles coming through the water 
stabilizes, count the number of bubbles appearing during 
a ten-second period. Each bubble appearing during a 
ten-second period represents a flow rate of 
approximately 0.001 cfh.
To meet code requirements, leakage must not exceed the 
values in Table 5.
Table 5. Allowable Leakage Rates.
a
Based on air standard conditions, test pressures in 
accordance with ANSI Z21.21, Section 2.4.2 and a maximum 
of 235 cc/h per inch of seal-off-diameter. Seal-off diameter is 
not the same as pipe size.
11. Close the upstream manual gas cock (A).
12. Close the test petcock (F), remove the test apparatus, 
and replace the leak test tap plug (D).
13. Open the upstream manual gas cock (A) and energize 
the safety shutoff valve (C).
14. Test with soap bubbles to make sure there is no leak at 
the test tap (D).
15. De-energize the safety shutoff valve (C).
16. Open the downstream manual gas cock (E).
17. Restore the system to normal operation.
Fig. 15. Valve leak test.
Pipe Size 
(in.)
Allowable
a
Leakage
Number of Bubbles 
per 10 sec.
1, 1-1/4
353
11 (Nat. gas), 7 (LP)
1-1/2, 2
453
14 (Nat. gas), 9 (LP)
M9547F
GAS
SUPPLY
UPSTREAM
MANUAL
GAS COCK
DOWNSTREAM
MANUAL
GAS COCK
BURNER
   D
A
B
C
E
F
PRV
MANUAL
TEST
PETCOCK
SSOV
1/4 IN. (6 MM) 
FLEXIBLE
TUBING
1/4 IN. (6 MM)
ALUMINUM OR 
COPPER PILOT 
TUBING
JAR OR GLASS
WITH WATER
CUT AT
45 DEGREE
ANGLE
CAN ALSO BE A PERMANENT PETCOCK.
PRV = PRESSURE REGULATING VALVE.
SSOV = SAFETY SHUTOFF VALVE.
 USE ONLY ONE OF THE DOWNSTREAM TAPS ON THE SS0V.
1
2
3
4
4
2
3
1
1
2
(13 MM)
LEAK 
TEST 
TAP