INSTALLATION INSTRUCTIONS
69-1484-2
T8400C1099, T8401C1031
Electronic Thermostats
The T8400 and T8401 Thermostats provide single-stage, 
non-programmable temperature control for 24V heating-
cooling systems with manual changeover from heat to 
cool. Heating cycle rate is selectable at 1, 3, 4, 5, 6, 9, or 
12 cph. Cooling cycle rate is fixed at 3 cph. Temperature 
indication can be set for °F or °C. 
The T8400 Thermostat is powered through the heating/
cooling system controls. The T8401 requires a common 
wire for operation. Batteries are not required because 
setpoints are held permanently by non-volatile memory.
The T8400 and T8401 models include a thermostat, 
wallplate (for wiring and mounting thermostat) and 
owner’s guide. 
MERCURY NOTICE
If this control is replacing a control that contains 
mercury in a sealed tube, do not place your old 
control in the trash.
Contact your local waste management authority 
for instructions regarding recycling and the 
proper disposal of an old control containing 
mercury in a sealed tube.
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow 
them could damage the product or cause a hazard-
ous condition.
2. Check the ratings given in the instructions and on 
the product to make sure the product is suitable for 
your application.
3. Installer must be a trained, experienced service 
technician.
4. After installation is complete, check out product 
operation as provided in these instructions.
CAUTION
Electrical Shock or Equipment Damage 
Hazard.
Can shock individuals or short equipment 
circuitry.
Disconnect power supply before installation.
Location
Install the thermostat about 5 ft (1.5m) above the floor in 
an area with good air circulation at average temperature. 
See Fig. 1. Do not install the thermostat where it can be 
affected by:
— drafts or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from the sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall 
behind the thermostat.
This thermostat is a precision instrument and was 
carefully adjusted at the factory. Handle it carefully.
Mounting Wallplate to Wall
IMPORTANT
Level only for appearance. The thermostat func-
tions normally even when not level.
Mount the T8400 and T8401 with the screws provided 
(see Fig. 2) as follows:
1. Place the wallplate at the desired location on the 
wall.
2. Pull the thermostat wire through the entrance hole 
on the wallplate.
3. Fasten the wallplate to the wall using the anchors 
and screws provided.
4. After wiring the wallplate, plug the hole to prevent 
drafts from affecting the thermostat; see Wiring 
section.