T6570, T8570 SERIES DIGITAL FAN-COIL THERMOSTATS 
Table 2. Electrical Rating 
50-60 Hz 
24V  120V  208V  230V  277V 
Amps (Resistive) 
3.8 
3.8 
3.8 
3.8 
3.8 
Full Load Inductive 
3.0 
3.0
3.0 
3.0 
3.0 
Pilot Duty 
100 VA
1
 Equivalent to NEMA 1/8 horsepower rating; allowable load 
must be determined by adding nameplate full load and locked 
rotor rating of all loads. 
Minimum Operational Life (at maximum load): Thermostat 
contacts (at 120 Vac): 100,000 cycles 
Manual Switches: 10,000 operations. 
M12081A 
3-11/16 
(94) 
4-3/16 (122) 
1-7/16 (37) 
1-1/2 
(38) 
3-5/16 (84) 
2-3/8 (60) 
Energy Savings Input: 24 Vdc dry contact, maximum resis-
tance of 1000 ohms. Note 'Caution', page 3. 
Protection Class: IP30. 
Approvals: CSA Certified C/US LR158158 for Canada and 
the U.S.A. Meets CE requirements. 
Accessories: Adapter plate for mounting on single- or double-
gang NEMA-standard vertical switch box: 
272878 - line voltage models, 24V 2000 series 
272881 - 24 V models, 1000 series 
T8109 - remote temperature sensor for 
T8575D W6380 - fan switching center for T8574/T8575 
products 
Fig. 1. Nominal dimensions in inches (mm) 
INSTALLATION 
When Installing this Product... 
1.   Read these instructions carefully. Failure to follow them 
could damage the product or cause a hazardous condi-
tion. 
2.   Check the ratings given in the instructions and on the 
product to make sure the product is suitable for your 
application. 
3.   Installer must be a trained, experienced service techni-
cian. 
4.   After installation is complete, check out product opera-
tion as provided in these instructions. 
CAUTION 
Electrical Shock or Equipment Damage Hazard. 
Can shock individuals or short equipment circuitry.
Disconnect power supply before installation. 
IMPORTANT 
T6570 Series are line voltage powered devices.
All wiring must comply with national and local electri-
cal codes, ordinances and regulations. 
Provide disconnect means and overload protec-
tion as required. 
T8570 Series thermostats
 must be powered by an 
Approved 24 Vac, Class 2 transformer (such as a 
W6380 Relay Control Center). 
Location 
The T6570, T8570 series thermostats are the temperature 
control element in a fan-coil or air-conditioning system. They 
must be located about 1.5m (5 ft.) above the floor in a position 
with good air circulation to sense room temperature. 
The optional T8109 sensor can be used to sense temperature 
in return air ductwork, instead of at the thermostat 
IMPORTANT 
Do not mount device where it can be affected by: 
1.   Drafts or dead spots behind doors or in corners. 
2.   Hot or cold air from ducts. 
3.   Radiant heat from the sun or appliances. 
4.   Unheated (uncooled) areas such as an outside wall 
behind the thermostat.  
5.   Concealed pipes or chimneys. 