Honeywell TH6220D 用户手册

下载
页码 20
FocusPRO
TH6220D Programmable Thermostat
13
10
0
Next
Done
To begin, press and hold the
and 
buttons until the display changes
System test
number
Press 
to turn on system
Press 
to turn off system
Press 
N
NE
EX
XT
T
to advance to next test
Press 
D
DO
ON
NE
E
to terminate system test
System
status
10
20
30
40
70
Heating system
Emergency 
heating system
Cooling system
Fan system
Thermostat
information
(for reference only)
0
Heat and fan turn off
1
Heat turns on. Fan also turns on immediately if Function 1 is set
to “1” or “5,” or if Function 3 is set to “1” 
**See page 11
2
Second stage heat turns on
0
Heat and fan turn off
1
Heat and fan turn on
2
Second stage heat turns on (Aux)
0
Compressor and fan turn off
1
Compressor and fan turn on
2
Second stage compressor turns on
0
Fan turns off
1
Fan turns on
71 Software revision number (major revisions)
72 Software revision number (minor revisions)
73 Configuration identification code (major)
74 Configuration identification code (minor)
75 Production configuration date code (week)
76 Production configuration date code (year)
System Test
System Status 
Installer system test
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection (minimum off time) is bypassed during testing. To prevent
equipment damage, avoid cycling the compressor quickly.
Follow the procedure below to test the heating, cooling and fan.
Installation Guide
12
1
0
8
9
10
12
13
14
15
16
27
28
Emergency heat
cycle rate (CPH)
Compressor
cycle rate (CPH)
Second stage 
compressor cycle
rate (CPH)
System setting
adjustment
Adaptive Intelli-
gent Recovery
Temperature 
display
Compressor 
protection
Schedule format
Heat temperature
range stops
Cool temperature
range stops
9 For electric emergency heat
1
For steam or gravity systems
3
For hot water systems & furnaces of over 90% efficiency
5
For gas or oil furnaces of less than 90% efficiency
[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
3 Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
3 Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
0 Manual changeover (Heat/Cool/Off)
1
Auto changeover (Heat/Cool/Auto/Off) 
**See page 14
2
Auto changeover only (Auto) 
**See page 14
1 On
**See page 14
0
Off
0 Fahrenheit
1
Celsius
5 Five-minute compressor off time 
**See page 14
[Other options: 0, 1, 2, 3 or 4-minute off time]
0 5/2 (programmable weekdays and weekends)
1
5/1/1 (weekdays, Saturday & Sunday programmable)
90
Highest heating temperature setting
40-89 Heating temperature range (increments of 1°F, or 0.5°C)
50
Lowest cooling temperature setting
51-99 Cooling temperature range (increments of 1°F, or 0.5°C)
Setup Function
Settings & Options
To begin, press and hold the and 
FFA
AN
N
buttons until the display changes
Function
number
Press or to 
change 
settings
Press 
N
NE
EX
XT
T
to advance to next function
Press 
D
DO
ON
NE
E
to exit and save settings
Setting
Installer setup
Next
Done
Follow the procedure below to configure the thermostat to match the installed
heating/cooling system, and customize feature operation as desired.