Honeywell V4062C 用户手册

下载
页码 8
V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR
60-2099—8
3
Table 4. Pressure Ratings of Valve-Actuators Combinations.
Auxiliary Switch And Proof-Of-Closure Switch Ratings:
See Table 5.
Table 5. Auxiliary Switch and Proof-of-Closure
Switch Ratings (1/2 hp [0.37 kW]
a
).
a
Maximum total connected power to both switches (if used)
is 1800 VA.
Mounting:
Mounts directly to V5055/V5097 Valve with two setscrews
positioned 90 degrees apart.
Valve and actuator can be mounted in any position
(multipoise).
NOTE:
220 to 240 Vac, 50/60 Hz models must be mounted
vertically.
Mounting Dimensions:
See Fig. 1.
Low-Fire Adjustment:
0.17 inch to 0.64 inch (with respect to V5055/V5097B
Valve) valve stem travel.
NOTE:
The low-fire position of the V5055/V5097A,C,D and
E Valves differ from the V5055/V5097B. Check the
valve flow curves and match the low-fire position to
the burner design and valve application.
Load
120V
240V
Full Load
9.8A
4.9A
Locked Rotor
58.8A
29.4A
Nominal Opening Time:
Standard Models: 26 sec at 60 Hz; 32 sec at 50 Hz.
Fast-opening Models: 13 sec at 60 Hz; 16 sec at 50 Hz.
Closing Time:
1 sec maximum
Damper Shaft:
3/8 in. sq (9.5 mm) for use with 7616BR Damper Crank
Arm (not included). Models available with or without
damper shaft return spring.
Maximum Damper Shaft Rotation:
52 angular degrees.
Maximum Force:
At 2-11/16 in. (68.3 mm) radius for 7616BR Damper
Crank Arm (ordered separately).
NOTE:
Damper shaft drives damper crank arm in one
direction only; optional return spring is available on
damper shaft to turn damper crank arm in opposite
direction. See Table 6.
Table 6. Actuator Torque (With and
Without Return Spring).
V4062
-40
°
F to 20
°
F
(-40
°
C to -7
°
C)
20
°
F to 150
°
F
(-70
°
C to 66
°
C)
Model
lb
N
lb
N
Without return
spring
5
22.2
20
89.0
With return spring
5
22.2
10
44.5
V4062A,D Actuator
a
V4062B Actuator
Differential
b
  
Closeoff
c
Differential
b
  
Closeoff
c
Valve
psi
mbar
psi
bar
psi
mbar
psi
bar
V5055A,C; V5097A,C 3/4 to 3 in.
5
340
15
1
15
1000
15
1
V5055A,C 4 in.
3
200
15
1
5
340
15
1
V5055B, V5097B 3/4 to 3 in.
5
340
15
1
15
1000
15
1
V5055B 4 in.
3
200
15
1
5
340
15
1
V5055D,E 3/4, 1, 1-1/4, 1-1/2 in.;
V5097D 3/4 in. to 2 in.
5
340
75
5
25
1700
75
5
V5055D,E; V5097D,E  2, 2-1/2, 3 in.
5
340
45
3
15
1000
45
3
a
Use a V4062D (with proof-of-closure switch) with a V5055/V5097C or E (with double seal) for valve seal  
overtravel interlock.
b
Maximum operating pressure differential.
c
Maximum closeoff pressure without seal leakage. this is the maximum allowable pressure drop to which a valve may be
subjected while fully closed, and is independent of the valve body rating.