Honeywell 1EN2R-9005 0406R3-NE 用户手册

下载
页码 22
EN2R-9005 0406R3-NE
12
L4191 - L6191 DUAL AQUASTAT - DIRECT IMMERSION
APPLICATION AND ORDERING INFORMATION
Application
L4191 and L6191 are dual units in which two independently 
working water temperature thermostats are housed in one 
cover. Each thermostat has a separate liquid filled sensing 
element which fits into a common immersion well for direct 
mounting into a boiler, tank or other vessel. One thermostat, 
with external temperature setting dial, acts as a controller 
while the other, with internal setting dial, acts as a high limit 
control.
Two main types are available, one with controller and auto 
recycling high limit and the other with controller and high limit 
with manual reset.
Ordering information L4191
1 =Gold contacts for thermocouple applications, without jumper
2 =High limit stop at 80°C/low limit stop at 60°C
3 =High limit stop at 82°C
4 =Low limit stop at 95°C
5 =Isolated neutral terminal
6 =High limit stop at 95°C
7 =With well assembly
8 =High limit stop
9 =With jumper
10 =With push-in plug
11 =Without knob and index
Ordering information L6191
1 =Gold contacts for thermocouple applications, without jumper
2 =High limit stop at 80°C/low limit stop at 60°C 
3 =High limit stop at 82°C
4 = Low limit stop at 95°C
5 = Isolated neutral terminal
6 = High limit stop at 95°C
7 = With well assembly
8 = High limit stop
9 = With jumper
10 =With push-in plug
11 = Without knob and index
O.S. number
Application
Temperature 
range
Switch   
differential (K)
Switch type
Setting means
Remarks   
(see notes)
L4191A 2002
Controller
25 ... 95°C
4
SPST
External knob
9
Limiter
25 ... 95°C
4
SPST
Internal screw
9
L4191A 2010
Controller
25 ... 95°C
4
SPST
External knob
7 - 9 - 10
Limiter
25 ... 95°C
4
SPST
Internal screw
9
L4191B 2018
Controller
70 ... 140°C
4
SPST
External knob
6
Limiter
70 ... 140°C
Manual reset
SPDT
Internal screw
1
L4191B 2042
Controller
25 ... 95°C
4
SPST
External knob
5 - 9 - 10
Limiter
25 ... 95°C
Manual reset
SPDT
Internal screw
9 - 10
O.S. number
Application
Temperature 
range
Switch   
differential (K)
Switch type
Setting means
Remarks   
(see notes)
L6191A 2007
Controller
40 ... 110°C
4 ... 10    
(adjustable)
SPDT
External knob
6 - 7 - 9 
Limiter
40 ... 110°C
4
SPDT
Internal screw
9
L6191A 2015
Controller
25 ... 95°C
4
SPDT
External knob
3
Limiter
101°C fixed
4
SPST
Internal setting
1
L6191A 2023
Controller
50 ... 95°C
4
SPDT
External knob
3
Limiter
101°C fixed
4
SPST
Internal screw
1
L6191B 2005
Controller
25 ... 95°C
4
SPDT
External knob
7 - 9 - 10
Limiter
40 ... 110°C
Manual reset
SPDT
Internal screw
9
L6191B 2013
Controller
40 ... 110°C
4
SPDT
External knob
5 - 6 - 7 - 9
Limiter
40 ... 110°C
Manual reset
SPDT
Internal screw
9
L6191B 2021
Controller
70 ... 140°C
4 ... 10   
(adjustable)
SPDT
External knob
4 - 7 - 9
Limiter
70 ... 140°C
Manual reset
SPDT
Internal screw
9
L6191B 2047
Controller
70 ... 140°C
4 ... 10   
(adjustable)
SPDT
External knob
4 - 7 - 9 - 11
Limiter
70 ... 140°C
Manual reset
SPDT
Internal screw
9
L6191B 2054
Controller
25 ... 95°C
4
SPDT
External knob
7 - 10
Limiter
50 ... 95°C
Manual reset
SPDT
Internal screw