CM900 Wireless - Programmable Room Thermostat
4.5.2 Category 2 - System Settings
Notes
1) Remember to always press the green   button to confirm that you want to store your new Installer Set-
Up setting. To exit the Installer Mode move the slider switch to the AuTO or MAN position.
2) These parameters are set centrally for the zoning system at the room thermostat configured as the 
system synchroniser.
3) Minimum on-time setting applies only to the boiler controller. All receiver box zone controllers will work 
with the minimum on-time of 30 seconds.
Parameter
Parameter 
No.
Factory Default Setting
Optional Setting
Category 2 Parameters – System Settings (press the 
 button to access this category)
Display
Description
Display  Description
Minimum boiler 
ON time
1:Ot
1
1 minute minimum 
ON time
2 to 5
Selection of 2, 3, 4 or 5 minutes 
minimum ON time
Cycle Rate
2:Cr
6
6 cycles per hour 
(cph)
3,9 or 
12
Selection of 3, 9 or 12 cph
Heat/Cool Change
4:HC
0
Disabled
1
Enabled
Pump Exercise
5:PE
0
Pump exercise 
disabled
1
Pump exercise enabled
System 
Synchronisation
6:Sn
0
Standard operation of 
the Room Unit
1
Room unit configured as Synchroniser
Loss of 
Communications 
Instruction
7:LC
0
Relay Off
1
Relay 20% on / 80% off
The following Parameters are for the control of other Honeywell Wireless products such as Wireless Underfloor Heating 
controls and Wireless Radiator controls. For more information please contact Honeywell sales.
Room Temperature 
Sensor Use
8:Su
0
HC60 control
1,2,3 
or 4
1 - HR80/HM80 control with own/remote 
sensor (no temperature displayed)
2 - Hr80/HM80/HCE80 control with CM 
sensor
3 - HC60 control and HR80/HM80/
HCE80 control with own/remote sensor
4 – Hr80/HM80/HCE80 control with own/
remote sensor (temperature displayed) 
HR80 Window-
Open Function
9:HO
0
Disabled
1
Enabled
HR80 Local 
Override
10:HL
1
Enabled
0
Disabled
Maximum Flow 
Setpoint
11:uF
55
55°C Maximum Flow 
Temp.
0 to 99
0°C to 99°C adjustment in 1°C steps
Minimum Flow 
Setpoint
12:LF
15
15°C Minimum Flow 
Temp.
0 to 50
0°C to 50°C adjustment in 1°C steps
Mixing Value Run 
Time
13:Ar
150
150 seconds
0 to 
240
0 to 240 sec. adjustment in 1sec steps
Pump Overrun Run 
Time
14:Pr
15
15 minutes
0 to 99
0 to 99 mins adjustment in 1min steps