gas piping
Contact your local gas service company to ensure that adequate 
gas  service  is  available  and  to  review  applicable  installation 
codes for your area.
Size the main gas line in accordance with Table 9. The figures shown 
are for straight lengths of pipe at 0.5 in. W.C. pressure drop, which is 
considered normal for low pressure systems. Note: Fittings such as 
elbows, tees and line regulators will add to the pipe pressure drop. 
Also refer to the latest version of the National Fuel Gas Code.
Schedule 40 Metallic Pipe is the preferred material for the gas 
line  of  this  water  heater.  It  is  imperative  to  follow  the  sizing 
recommendations in the latest version of the National Fuel Gas 
Code if Corrugated Stainless Steel Tubing (CSST) is used as the 
gas line for this water heater.
The heATer IS NOT INTeNDeD FOr OPerATION AT hIGher 
ThAN  14.0”  W.C.-  NATUrAL  GAS,  (1/2  POUND  Per  SQUAre 
INCh  GAGe)  SUPPLy  GAS  PreSSUre.  eXPOSUre  TO 
hIGher  SUPPLy  PreSSUre  MAy  CAUSe  DAMAGe  TO  The 
GAS VALVe WhICh COULD reSULT IN FIre Or eXPLOSION. 
IF  OVerPreSSUre  hAS  OCCUrreD  SUCh  AS  ThrOUGh 
IMPrOPer  TeSTING  OF  GAS  LINeS  Or  eMerGeNCy 
MALFUNCTION  OF  The  SUPPLy  SySTeM,  The  GAS  VALVe 
MUST Be CheCkeD FOr SAFe OPerATION. MAke SUre ThAT 
The OUTSIDe VeNTS ON The SUPPLy reGULATOrS AND The 
SAFeTy VeNT VALVeS Are PrOTeCTeD AGAINST BLOCkAGe. 
TheSe Are PArTS OF The GAS SUPPLy SySTeM, NOT The 
heATer. VeNT BLOCkAGe MAy OCCUr DUrING ICe STOrMS.
taBle 9 - gas supply pipe length (feet)
Schedule 40 metallic 
pipe nominal dia.
500,000 btu/hr input rate 
MAXIMUM eQUIVALeNT PIPe LeNGTh (FeeT)
Natural Gas
Propane
3/4"
-
10
1"
10
40
1 1/4"
60
150
1 1/2"
150
350
2"
200
400
2 1/2"
200
400
Natural Gas: 0.60 Specific Gravity, 0.50"W.C. pressure drop
Propane Gas: 1.50 Specific Gravity, 0.50"W.C. pressure drop
IT IS IMPOrTANT TO GUArD AGAINST GAS VALVe FOULING 
FrOM CONTAMINANTS IN The GAS WAyS.  SUCh FOULING 
MAy CAUSe IMPrOPer OPerATION, FIre Or eXPLOSION.
IF  COPPer  SUPPLy  LINeS Are  USeD  They  MUST  Be 
INTerNALLy TINNeD AND CerTIFIeD FOr GAS SerVICe. 
BeFOre ATTAChING The GAS LINe, Be SUre ThAT ALL GAS 
PIPe IS CLeAN ON The INSIDe.
TO TrAP ANy  DIrT  Or  FOreIGN  MATerIAL  IN The  GAS 
SUPPLy LINe, A DIrT LeG (SOMeTIMeS CALLeD SeDIMeNT 
TrAP  Or  DrIP  LeG)  MUST  Be  INCOrPOrATeD  IN  The 
PIPING  (See  FIG.  21). The  DIrT  LeG  MUST  Be  reADILy 
ACCeSSIBLe AND NOT SUBJeCT TO FreeZING CONDITIONS.  
INSTALL  IN ACCOrDANCe  WITh  reCOMMeNDATIONS  OF 
SerVING GAS SUPPLIerS.  reFer TO The LATeST VerSION 
OF The NATIONAL FUeL GAS CODe.  
To prevent damage, care must be taken not to apply too much 
torque when attaching gas supply pipe to gas valve inlet.
Apply joint compounds (pipe dope) sparingly and only to the male 
threads of pipe joints.  Do not apply compounds to the first two threads.  
Use compounds resistant to the action of liquefied petroleum gases.
BeFOre PLACING The heATer IN OPerATION, CheCk FOr 
GAS LeAkAGe.  Use soap and water solution or other material 
acceptable for the purpose in locating the leaks. DO NOT USe 
MATCheS,  CANDLeS,  FLAMe  Or  OTher  SOUrCeS  OF 
IGNITION FOr ThIS PUrPOSe.
DISCONNeCT The heATer AND ITS MANUAL GAS ShUTOFF 
VALVe FrOM The GAS SUPPLy PIPING SySTeM DUrING ANy 
SUPPLy PreSSUre TeSTING eXCeeDING 1/2 PSIG.  GAS 
SUPPLy  LINe  MUST  Be  CAPPeD  WheN  DISCONNeCTeD 
FrOM The heATer. FOr TeST PreSSUreS OF 1/2 PSIG Or 
LeSS The APPLIANCe NeeD NOT Be DISCONNeCTeD, BUT 
MUST Be ISOLATeD FrOM The SUPPLy PreSSUre TeST 
By CLOSING The MANUAL GAS ShUTOFF VALVe.
gas piping and dirt leg installation
figure 21
purging
Gas line purging is required with new piping or systems in which 
air has entered.
PUrGING  ShOULD  Be  PerFOrMeD  By  PerSONS 
eXPerIeNCeD IN ThIS TyPe GAS SerVICe. TO AVOID rISk 
OF  FIre  Or  eXPLOSION,  PUrGe  DISChArGe  MUST  NOT 
eNTer CONFINeD AreAS Or SPACeS Where IGNITION CAN 
OCCUr. The AreA  MUST  Be  WeLL  VeNTILATeD AND ALL 
SOUrCeS OF IGNITION MUST Be INACTIVATeD Or reMOVeD.
gas meter siZe — natural gases only
Be sure the gas meter has sufficient capacity to supply the full 
rated gas input of the water heater as well as the requirements of 
all other gas fired equipment supplied by the meter.  If gas meter 
is too small, ask the gas company to install a larger meter having 
adequate capacity.
gas pressure regulator
The gas pressure regulator is built into the gas valve and is equipped to 
operate on the gas specified on model and rating plate. The regulator 
is factory adjusted to deliver gas to burner at correct water column 
pressure allowing for a nominal pressure drop through the controls.
The minimum gas supply pressure for input adjustment must not 
be less than 4.5” W.C. (1.12 kPa) for natural gas or 11.0"W.C. 
(2.74 kPa) for propane gas. 
Do  not  subject  the  combination  gas  valve  to  inlet  gas  
pressures of more than 14.0” W.C. (3.48 kPa). A service regulator 
is necessary if higher gas pressures are encountered.
The manifold gas pressure specified in Table 10 refers to the gas 
pressure measured at the pressure tap of the automatic gas valve 
when the burners are firing.
taBle 10 - manifold gas pressure in inches of 
water column (all models*)
type of gas
natural
propane
3.5 (0.87 kPa)
10.0 (2.49 kPa)