EC2-391 Display Case and Coldroom Controller 
Operating Instructions 
GB 
List of Parameters 
 
/ DISPLAY 
PARAMETERS 
Min Max  Unit Def. Custom
/1  Value to show 
0   
  0 = Thermostat control temperature with Temp. alignment °C 
1 = Air-in temperature °C 
2 = Air-out temperature °C 
3 = Alarm temperature °C 
4 = Defrost termination temperature °C 
5 = Coil-in temperature °C  
6 = Coil-out temperature °C 
7 = Calculated superheat °K 
8 = Valve opening in % 
9 = Displays defrost status 
         
/2  Alarm suppression   0 = off, 1 = on 
0   
/5  Temperature Unit  
0 = °C, 1 = °F 
0   
/6  Decimal point  
0 = yes, 1 = no 
0   
/7  Display during defrost 
0   
  0 = dF (= defrost mode);   1 = dF + defrost termination temp. 
 
2 = dF + control temperature 
         
/C  Temperature alignment  for /1=0 
-20 
20 
K / °F  0.0   
A ALARM-PARAMETERS 
 
 
 
 
 
A0  Mean factor alarm temperature 
100 
100   
A1  Low temp alarm delay 
180 
min 
5   
A2  High temp alarm delay 
180 
min 
5   
A3  Alarm delay after defrost 
180 
min 
10   
AH 
High temp alarm limit 
AL 
70 
°C / K 
40   
AL  Low temp alarm limit 
-55  AH  °C / K  -50   
At  Alarm limit type 
0   
  0=absolute temperatures °C; 1= relative temperatures K to setpoint          
r THERMOSTAT-PARAMETERS 
r1 Min setpoint 
-50  r2 
°C 
-50   
r2 Setpoint max 
r1  60 
°C 
40   
r3  Day/night control   
0 = off, 1 = on 
1   
r4 Thermostat mode 
1   
  0 = off, no thermostat function, continues cooling air in sensor monitoring 
off, no temp. alarms generated  
1 = cooling, deadband control: 
cut in   = set-point + difference   
 
cut out = set-point 
2 = cooling, modulating thermostat:  cut in   = set-point   
 
cut out = set-point – difference /2 
3 = heating, deadband control: 
cut in   = set-point – difference  
 
cut out = set-point 
4 = on, external control using nvi Valve via SNMP. Air in and air out sensor 
 
monitoring off. Temp. alarms will be generated 
 
r6 Setpoint night 
r1  r2 
°C 
4.0   
r7 Differential night 
0.1  20.0 
2.0   
r8  Mean factor, day operation 
100 
100 
 
r9  Mean factor, night operation 
100 
50 
 
rd Differential day 
0.1  20.0 
2.0   
St Setpoint day 
r1  r2 
°C 
2.0   
d DEFROST 
PARAMETERS 
 
 
 
 
 
d0 Defrost mode 
1   
  0 = natural defrost, defrost heater not activated 
pulsed defrost not possible 
1 = forced defrost, defrost heater activated, pulsed 
defrost possible 
2 = forced defrost, defrost heater activated, pulsed defrost possible, 
defrost termination using nviStartUp via SNMP 
         
d1  Termination by:  
0   
  0 = termination by temperature,  
termination by time will generate an alarm 
1 = termination by time,  
termination by temperature will generate an alarm 
2 = first, what ever comes first time or temperature, no alarm 
3 = last, by time and temperature, no alarm 
         
d2  Defrost termination sensor  
 
  0 = Dedicated defrost sensor must be installed 
1 = Air-out sensor used for defrost termination 
         
d3 Pulsed defrost 
0   
  0 = off, no pulsed defrost, heaters switched off at defrost termination 
temperature dt or max. time dP whatever is selected  
1 = on, pulsed defrost, dd and dH in use, heaters are switched off at 
dH and switched on again at  dH – dd 
         
d4  Defrost at startup  
0 = no, 1 = yes 
0   
d5  Delay power up defrost 
180 
min 
0   
 
   
Min  Max  Unit Def. Custom
d6 Pump down delay 
180 
sec 
0   
  Compressor will run during pump down delay while valve is closed           
d7 Drain delay 
15 
min 
2   
d8 Injection delay 
180 
sec 
0   
  Valve is open during injection delay while compressor is not running          
d9 Demand defrost mode 
0 = off, 1 = on, 2 = on together with 
timed defrost 
0 2  -  0 
 
dd Pulsed defrost differential 
20 
2   
dH Pulsed defrost setpoint 
-40 
dt 
°C 
5   
dt  Defrost termination temperature 
-40 
90 
°C 
8   
dP Max defrost duration 
180 
min 
30   
dI Defrost interval 
192 
8   
du Start up delay after synch 
180 
min 
30   
F FAN-PARAMETERS 
 
 
 
 
 
F1 Fan startup by:   
0 = on  
0   
  1 = delayed by time Fd, error on temperature 
2 = by temperature Ft, error on time 
3 = first, whatever comes first time or temperature, no alarm 
4 = last, time and temperature must come, no alarm 
         
F2 During no cooling  
0   
  0 = on; 1 = off; 2 = delayed by F4; 3 = off, when door open 
         
F3 During defrost  
0 = on, 1 = off 
0   
F4 Stop delay time  
30 
min 
0   
F5 During cleaning   
0 = off, 1 = on 
0   
Fd Fan delay after defrost 
30 
min 
0   
Ft On temp after defrost 
-40 
40 
°C 
0   
u SUPERHEAT 
PARAMETERS 
u0 Refrigerant  0 = R22 
1 = R134a  
2 = R507 
3 = R404A  4 = R407C  
5 = R410A  6 = R124 
7 = R744A 
0 7  -  3 
 
u1 Correction glide / dp 
Glide              = positive  values 
Pressure drop = negative values 
-20.0 20.0 
0.0   
u2 MOP control 
 
0 = MOP off, 1 = MOP on 
0 1  -  0 
 
u3 MOP temperature 
-40 
40 
°C 
0   
u4 Superheat mode  
0 = off 
1 = fixed superheat 
2 = adaptive superheat 
0 2  -  1 
 
u5 Superheat init setpoint 
u6 
u7 
6   
u6 Superheat setpoint min. 
u7 
3   
u7 Superheat setpoint max. 
u6 
20 
15   
uu Start 
opening 
25 
75 % 30 
 
 DIGITAL 
INPUT 
PARAMETERS 
i0  S5 input 
1 = inverse function 
0   
∩0 Functions for S5  0 = normal input 
0   
  1 = cleaning 
2 = only fan 
3 = door contact 
4 = permanent cooling 
5 = day / night switch 
6 = compressor safety chain 
7 = defrost request 
8 = defrost inhibited 
       
 DIGITAL 
OUTPUT 
PARAMETERS 
o0 Output 
1 = inverse function 
0   
n0 Functions for output  1 = alarm 
0   
H OTHER PARAMETERS 
 
 
 
 
 
H2 Display access 
 
3   
  0 = all disabled (Caution: access to controller only via LON 
network possible) 
1 = Keyboard enabled 
2 = IR remote control enabled 
3 = Keyboard and IR remote control; Temporary data display and 
manual defrost enabled. 
4 = Keyboard and IR remote control; Temporary data display 
disabled. Control setpoint with SEL key and manual defrost 
enabled. 
         
H3 IR access code 
199 
0   
H5 Password 0 
199 
12