SPX Cooling Technologies TG MAG23-65 用户手册

下载
页码 72
11
A.0500.551 – IM-TGMAG/02.00 EN (02/2008)
1.4  Technical conventions
Quantity
Symbol
Unit
Dynamic viscosity
µ
mPa.s = cP (Centipoise)
Kinematic viscosity
ν = µ
     
 ρ
ρ = density   
[ ]
kg
dm
3
ν = kinematic viscosity   
[ ]
mm
2
s
= cSt (Centistokes)
Note! In this manual only dynamic viscosity is used.
Pressure
p
[bar]
∆p
Differential pressure = [bar]
p
m
Maximum pressure at discharge flange (design pressure) = [bar]
Note! In this manual, unless otherwise specified - pressure is relative pressure [bar].
Net Positive  
SuctionHead
NPSHa
Net Positive Suction Head is the total absolute inlet pressure at 
the pump suction connection, minus the vapour pressure of the 
pumped liquid.
NPSHa is expressed in meter liquid column. 
It is the responsibility of the user to determine the NPSHa value.
NPSHr
Net Positive Suction Head Required is the NPSH determined, 
after testing and calculation, by the pump manufacturer to avoid 
performance impairment due to cavitation within the pump at rate 
capacity.
The NPSHr is measured at the suction flange, at the point where 
the capacity drop results in a pressure loss of at least 4%.
Note! In this manual, unless otherwise specified, NHPH = NPSHr
When selecting a pump, ensure that NPSHa is at least 1 m higher than the NPSHr.