CHAPTER 5:  Configuration
 
37
•  Power Configuration:  In the Web Browser Interface, the Voltage Calibration 
parameter, Power Factor parameter and Power Efficiency parameter are defined 
via the System Parameters Menu.  In the Text Interface, these parameters reside 
in a separate submenu, which is accessed via the Power Configuration option.  
For more information on Power Configuration, please refer to Section 5.3.5.
5.3.1.  The Real Time Clock and Calendar
The Real Time Clock menu is used to set the Outlet Managed PDU’s internal clock 
and calendar.  The configuration menu for the Real Time Clock offers the  
following options:
•  Date:  Sets the Month, Date, Year and day of the week for the Outlet Managed 
PDU’s real-time clock/calendar.
•  Time:  Sets the Hour, Minute and Second for the Outlet Managed PDU’s real 
time clock/calendar.  Key in the time using the 24-hour (military) format.
•  Time Zone:  Sets the time zone, relative to Greenwich Mean Time.  Note that 
the Time Zone setting will function differently, depending upon whether or not 
the NTP feature is enabled and properly configured.   
(Default = GMT (No DST).)
  NTP Enabled:  The Time Zone setting is used to adjust the Greenwich Mean 
Time value (received from the NTP server) in order to determine the precise 
local time for the selected time zone.
  NTP Disabled:  If NTP is disabled, or if the Outlet Managed PDU is not able 
to access the NTP server, then status screens and activity logs will list the 
selected Time Zone and current Real Time Clock value, but will not apply 
the correction factor to the displayed Real Time Clock value.
•  NTP Enable:  When enabled, the Outlet Managed PDU will contact an NTP 
server (defined via the NTP Address prompts) once a day, and update its clock 
based on the NTP server time and selected Time Zone.  (Default = Off.)
Notes:
•  The Outlet Managed PDU will also contact the NTP server and 
update the time whenever you change NTP parameters.
•  To cause Outlet Managed PDU to immediately contact the NTP 
server at any time, make certain that the NTP feature is enabled 
and configured, then type /F and press [Enter].  When the System 
Parameters menu appears, press [Esc].  The Outlet Managed PDU 
will save parameters and then attempt to contact the server, as 
specified by currently defined NTP parameters.