Generac QT02515ANSX 用户手册

下载
页码 9
3 of 9
25 • 30 • 45 • 60 kW 
operating data
GENERATOR OUTPUT VOLTAGE/kW - 60Hz
kW LPG
Amp LPG
kW Nat. Gas
Amp Nat. Gas
CB Size (Both)
QT025
120/240 V, 1Ø, 1.0 pf
25
104
25
104
125
120/208 V, 3Ø, 0.8 pf
25
87
25
87
100
120/240 V, 3Ø, 0.8 pf
25
75
25
75
90
QT030
120/240 V, 1Ø, 1.0 pf
30
125
30
125
150
120/208 V, 3Ø, 0.8 pf
30
104
30
104
125
120/240 V, 3Ø, 0.8 pf
30
90
30
90
100
QT045
120/240 V, 1Ø, 1.0 pf
45
188
45
188
200
120/208 V, 3Ø, 0.8 pf
45
156
45
156
175
120/240 V, 3Ø, 0.8 pf
45
135
45
135
150
277/480 V, 3Ø, 0.8 pf
45
68
45
68
80
QT060
120/240 V, 1Ø, 1.0 pf
60
250
60
250
300
120/208 V, 3Ø, 0.8 pf
60
208
60
208
250
120/240 V, 3Ø, 0.8 pf
60
180
60
180
200
277/480 V, 3Ø, 0.8 pf
60
90
60
90
100
SURGE CAPACITY IN AMPS
Voltage Dip @ < .4 pf
15%
30%
QT025
120/240 V, 1Ø
86
209
120/208 V, 3Ø
84
204
120/240 V, 3Ø
73
177
QT030
120/240 V, 1Ø
109
264
120/208 V, 3Ø
109
264
120/240 V, 3Ø
94
229
QT045
120/240 V, 1Ø
61
153
120/208 V, 3Ø
64
160
120/240 V, 3Ø
55
139
277/480 V, 3Ø
29
72
QT060
120/240 V, 1Ø
95
237
120/208 V, 3Ø
100
251
120/240 V, 3Ø
87
218
277/480 V, 3Ø
42
105
ENGINE FUEL CONSUMPTION
Natural Gas
Propane
(ft³/hr)
(m³ /hr)
(gal/hr)
(l/hr)
QT025
Exercise cycle
60
1.7
0.7
2.5
25% of rated load
220
6.3
2.9
9.1
50% of rated load
297
8.4
3.3
12.3
75% of rated load
362
10.3
4
15
100% of rated load
430
12.2
4.7
17.8
QT030
Exercise cycle
60
1.7
0.7
2.5
25% of rated load
240
6.8
2.6
10
50% of rated load
320
9.1
3.5
13.3
75% of rated load
400
11.4
4.4
16.6
100% of rated load
492
14
5.4
20.4
QT045
Exercise cycle
65
1.8
0.7
2.6
25% of rated load
210
6
2.3
8.6
50% of rated load
380
10.8
4.2
15.7
75% of rated load
545
15.5
5.9
22.4
100% of rated load
730
20.7
8
30.1
QT060
Exercise cycle
123
3.5
1.34
5.1
25% of rated load
267
7.6
2.7
10.5
50% of rated load
483
13.7
5
19
75% of rated load
672
19.1
7
26.5
100% of rated load
862
24.5
9
33.9
Guardian
®
 Series
STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage.  There 
is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.
Note: Fuel pipe must be sized for full load. 
For Btu content, multiply ft
3
/hr x 2520 (LP) or ft
3
/hr x 1000 (NG) 
For megajoule content, multiple m³/hr x 93.89 (LP) or m³/hr x 37.26 (NG)
Refer to "Emissions Data Sheets" for maximum fuel flow for EPA and SCAQMD permitting purposes.