Mitsubishi 51S-P626 用户手册

下载
页码 4
MITSUBISHI MGS SERIES 
DIESEL GENERATOR SET 
MGS1500HV 
 
 
 
 
Type & Design 
MGS  original  design,  double  bearings,  4  pole,  screen  protected,  selfexciting,  self  regulating  and  brushless  with  fully 
connected  damper  windings,  salient  pole  rotors,  A.C.  exciter  and  rotating  rectifier  unit.    Direct  coupled  to  engine  and 
regreaseable bearing, direct drive centrifugal blower. 
With space heater. 
Enclosure: Drip-proof IP22 
Terminal box: Totally enclosed IP44 
 
Winding System 
Standard 6 wire winding is provided.    All windings are formed wound and impregnated in vacuum pressure with a special 
epoxy resin. 
Overspeed capability: 125% for 2 minutes 
Insulation: Class 'F' of IEC 
Temperature rise: 130°C(Stand-by) 
Temperature rise: 105°C(Prime) 
 
Voltage Regulator 
Fully sealed, 3 phase RMS sensing AVR with built-in protection against sustained over-excitation.    This de-excites the 
generator after a minimum of 5 seconds. 
Voltage regulation: Less than +/- 0.5% from no load to full load at any power factor between 0.8 lagging and 1.0 
allowing for a 4% engine speed variation 
Voltage adjustment: +/- 6% 
Wave form: Less than 5% deviation 
 
Permanent Magnet Generator (PMG) 
Electrically isolated from the main alternator stator windings powers AVR - sustaining approx. 250% of short circuit current 
at the AC generator output terminals for not more than 10 seconds by means of excitation voltage via AVR 
 
Sensors 
Temperature sensors are provided as follows. 
Stator winding, 2 per each phase, PT100 
Bearing, 1 per each bearing, PT100 
 
Electrical Design 
In  accordance  with  BS5000  Part  3,  VDE0530,  UTE51100,  NEMA  MG1-22,  CEMA,  IEC34-1,  CSA22.2,  AS1359  and 
JEC2100. 
Telephone Influence Factor (TIF): Less than 50 
Telephone Harmonic factor (THF): Less than 2.5% 
Radio interference: Suppression is in line with the provision of VDE Class G and N 
 
 
Gen Set Option Features 
■  ENGINE 
Air Cleaner, paper element dry type 
Battery Kit 
Battery Charger 
Anchor Bolts 
 
■  FUEL 
Fuel Day Service Tank 
 
■  COOLING 
Heat Exchanger 
Expansion Tank 
Jacket Water Heater 
Removal STD Radiator, Fan & Fan Drive 
 
■  LUBRICATION 
Lub. Oil Priming Pump 
 
■  EXHAUST 
Exhaust Silencer 
Exhaust Flexible Pipe 
■  GENERATOR 
Power Factor Regulator 
 
■  CONTROL PANEL 
Diesel Generator Integrated Communication Synthesizer (DGICS-MII) 
Auxiliary Control Panel 
Remote Monitor Interface 
Temperature Meter for Winding & Bearing 
 
■  SWITCHGEAR 
Circuit Breaker VCB 
Reverse Power Relay 
 
 
 
 
 
Power Systems Engine Section, Engine Sales Department 
16-5, KONAN 2-CHOME, MINATO-KU, TOKYO 108-8215 JAPAN 
TEL: 81-3-6716-4771    FAX: 81-3-6716-5854 
Mitsubishi Heavy Industries, Ltd. serves for the customers with improved products continually. 
Therefore specification and some materials will be changed without notice. 
The International System of units (SI) is used in this publication.
 
MGS SERIES AC GENERATOR MODEL:  MG-KP626(STAND-BY) 
 
MG-KP626(PRIME)