page 28 — DCa25SSIU3 (wITh MLT25 SerIeS) • operaTIon anD parTS ManUaL — rev. #1 (01/24/13) 
inspectiOn/setup
CIrCUIT BreaKerS
To protect the generator from an overload, a 3-pole, 60 amp, 
main circuit breaker is provided to protect the 
U,v, and w 
output Terminals from overload. In addition two single-
pole, 20 amp 
gFCI circuit breakers are provided to protect 
the GFCI receptacles from overload. Two 50 amp circuit 
breakers have also been provided to protect the auxiliary 
receptacles from overload. Make sure to switch 
aLL circuit 
breakers to the 
oFF position prior to starting the engine.
LUBrICaTIon oIL
Fill the engine crankcase with lubricating oil through the 
filler hole, but 
Do noT overfill. Make sure the generator is 
level and verify that the oil level is maintained between the 
two notches (Figure 28) on the dipstick. See Table 11 for 
proper selection of engine oil.
Figure 28. Engine Oil Dipstick
When checking the engine oil, be sure to check if the oil is 
clean. If the oil is not clean, drain the oil by removing the 
oil drain plug, and refill with the specified amount of oil as 
outlined in the 
ISUZU engine owner’s Manual. Oil should 
be warm before draining.
Other types of motor oils may be substituted if they meet 
the following requirements:
 
„
 API Service Classification CC/SC
 
„
API Service Classification CC/SD
 
„
API Service Classification CC/SE
 
„
API Service Classification CC/SF
Table 11. recommended Motor oil
FUeL CheCK
refilling the Fuel System 
This generator has a fuel tank located inside the trailer 
frame. (Figure 29). 
aLwaYS fill the fuel tank with clean fresh 
#2 diesel fuel. Do noT fill the fuel tank beyond its capacity.
Pay attention to the fuel tank capacity when replenishing 
fuel. The fuel tank cap must be closed tightly after filling. 
Handle  fuel  in  a  safe  container.  If  the  container  does 
not have a spout, use a funnel. Wipe up any spilled fuel 
immediately.
Figure 29. Trailer Fuel Tank
  Danger
Fuel spillage on a 
hot engine can cause 
fire or explosion. If fuel spillage occurs, 
wipe  up  the  spilled  fuel  completely  to 
prevent  fire  hazards. 
never  smoke 
around or near the generator.
  CaUTIon
onLY  properly  trained  personnel  who  have  read 
and understood this section should refill the fuel tank 
system.
FUEL TANK
FILLER NECK