Multiquip DCA45SSI 用户手册

下载
页码 4
dca45ssi — MQ POWER sERiEs gEnERatOR — REv. #12 (08/23/11)
 DCA45SSI
 
MQ POWER Series Generator
WhisperWatt™
Prime Rating — 36 kW (45 kVA) 
standby Rating — 40 kW (50 kVA)
Three-Phase, 60 Hertz, 0.8 PF
45
standaRd FEatuREs
 
„
Heavy duty, 4-cycle, direct injection, diesel engine provides 
maximum reliability. 
 
„
Brushless  alternator  reduces  service  and  maintenance 
requirements and meets temperature rise standards for Class 
H insulation systems.
 
„
Open  delta  excitation  design  provides  virtually  unlimited 
excitation for maximum motor starting capability.
 
„
Automatic voltage regulator (AVR) provides precise regulation.
 
„
Electronic Governor Control — maintains frequency to within 
±0.25% from no load to full load.
 
„
Full load acceptance of standby nameplate rating in one step 
(NFPA 110, para 5-13.2.6).
 
„
Sound attenuated, weather resistant, steel housing provides 
operation at 65 dB(A) at 23 feet.  Fully lockable enclosure 
allows safe unattended operation.
 
„
Internal fuel tank with direct reading of fuel gauge.
 
„
Seven stage powder coat paint system provides durability 
and weather protection.
 
„
Fuel/water  separator  removes  condensation  from  fuel  for 
extended engine life. Panel mounted alarm light included.
 
„
Complete  engine  analog  instrumentation  includes  DC 
ammeter, oil pressure gauge, water temp. gauge, fuel level 
gauge, tachometer/hour meter, preheat indicator, emergency 
shutdown monitors.
 
„
Automatic  start/stop  control  —  automatically  starts  the 
generator set during a commercial power failure when used 
in conjunction with a transfer switch.
 
„
Complete generator analog instrumentation includes voltage 
regulator control, ammeter phase selector switch, voltmeter 
phase selector switch, AC voltmeter, AC ammeter, frequency 
meter, panel light, and circuit breaker.
 
„
Automatic  safety  shutdown  system  monitors  the  water 
temperature, engine oil pressure, overspeed and overcrank. 
Warning lights indicate abnormal conditions.
 
„
Complete power panel.  Fully covered; three-phase terminals 
and  single  phase  receptacles  allow  fast  and  convenient 
hookup  for  most  applications  including  temporary  power 
boxes, tools and lighting equipment. The GFCI receptacles 
are NEMA 5-20, and the auxilillary outputs use CS6369 twist-
lock receptacles.
 
„
Simultaneous single and three phase power.
 
„
Voltage selector switch offers the operator a wide range of 
voltages  that  are  manually  selectable.  Fine  tuning  of  the 
output voltage can be accomplished by adjusting the voltage 
regulator control knob to obtain the desired voltage.
 
„
EPA emissions certified - Interim Tier 4 emissions compliant.