Section 3 — Operation
Air-cooled 11 kW Generators
3.5  SETTING THE EXERCISE TIMER
This generator is equipped with an exercise timer. 
Once it is set, the generator will start and exercise 
once every seven days, on the day of the week and at 
the time of day the following sequence is completed. 
During this exercise period, the unit runs for approx-
imately 12 minutes and then shuts down. Transfer of 
loads to the generator output does not occur during 
the exercise cycle.
A switch on the control panel (see Figure 3.1) per-
mits selection of the day and time for the system to 
exercise. At the chosen time, perform the following 
sequence to select the desired day and time of day the 
system will exercise.
Place the AUTO/OFF/MANUAL switch in the AUTO 
position. Push and hold the “Set Exercise Time” 
switch to the ON position for approximately three 
seconds and release. All five red LED’s will flash for 
10 seconds. The unit will perform the standard exer-
cise sequence, then shut down. The generator will 
now exercise every seven days at the time set.
NOTE:
The exerciser will only work in the AUTO mode 
and will not work unless this procedure is per-
formed. The exerciser will need to be reset every 
time the 12-volt battery is disconnected and then 
reconnected.
3.6 PROTECTION 
SYSTEMS
3.6.1  LOW OIL PRESSURE SWITCH
This switch (Figure 3.2) has normally closed con-
tacts that are held open by engine oil pressure dur-
ing cranking and operating. Should oil pressure 
drop below the 8 psi range, switch contacts close, 
and the engine shuts down. The unit should not be 
restarted until oil is added. The AUTO/OFF/MANUAL 
switch must then be turned to OFF and then back to 
AUTO.
3.6.2  HIGH TEMPERATURE SWITCH
This switch’s contacts (Figure 3.3) close if the tem-
perature should exceed approximately 132º C (270º 
F), initiating an engine shutdown. The generator will 
automatically restart and the LED on the generator 
control panel will reset once the temperature has 
returned to a safe operating level.
‹
‹
Figure 3.2 – Low Oil Pressure and 
High Temperature Switches
3.6.3 OVERCRANK
This feature prevents the generator from damaging 
itself when it continually attempts to start and anoth-
er problem, such as no fuel supply, prevents it from 
starting. The unit will crank and rest for a preset 
time limit. Then, it will stop cranking, and the LED 
on the generator control panel will light indicating an 
overcrank failure. The AUTO/OFF/MANUAL switch 
will need to be set to OFF and then back to AUTO to 
reset the generator control board.
NOTE:
If the fault is not repaired, the overcrank feature 
will continue to activate.
3.6.3.1   Approximate Crank Cycle Times
• 15 seconds ON
• 7 seconds OFF
• 7 seconds ON
• 7 seconds OFF
•  Repeat for 45 seconds
  Approximately 90 seconds total
3.6.4 OVERSPEED
This feature protects the generator from damage by 
shutting it down if it happens to run faster than the 
preset limit. This protection also prevents the gen-
erator from supplying an output that could poten-
tially damage appliances connected to the generator 
circuit. Contact the nearest Authorized Dealer if this 
failure occurs.
‹
‹