11
FP-AI-110 and cFP-AI-110
Operate the [c]FP-AI-110 only at or below Pollution Degree 2. 
Pollution Degree 2 means that only nonconductive pollution 
occurs in most cases. Occasionally, however, a temporary 
conductivity caused by condensation must be expected.
Operate the [c]FP-AI-110 at or below Measurement 
Category II. Measurement Category II is for measurements 
performed on circuits directly connected to the low-voltage 
installation. This category refers to local-level distribution, 
such as that provided by a standard wall outlet.
Safety Guidelines for Hazardous Locations
The [c]FP-AI-110 is suitable for use in Class I, Division 2, Groups 
A, B, C, and D hazardous locations; Class 1, Zone 2, AEx nC IIC 
T4 and Ex nC IIC T4 hazardous locations; and nonhazardous 
locations only. Follow these guidelines if you are installing the 
[c]FP-AI-110 in a potentially explosive environment. Failing to 
follow these guidelines may result in serious injury or death.
Caution
Do not disconnect I/O-side wires or connectors 
unless power has been switched off or the area is known 
to be nonhazardous.
Caution
Do not remove modules unless power has been 
switched off or the area is known to be nonhazardous.
Caution
Substitution of components may impair 
suitability for Class I, Division 2.
Caution
For Zone 2 applications, install the Compact 
FieldPoint system in an enclosure rated to at least IP 54 
as defined by IEC 60529 and EN 60529.
Special Conditions for Safe Use in Europe
This equipment has been evaluated as EEx nC IIC T4 equipment 
under DEMKO Certificate No. 03 ATEX 0251502X. Each module 
is marked 
 II 3G and is suitable for use in Zone 2 hazardous 
locations.
Caution
For Zone 2 applications, connected signals must 
be within the following limits:
Capacitance .......................... 20 
µF max
Inductance ............................ 0.2 H max