National Instruments 9201 用户手册
NI 9201/9221
6
ni.com
Caution
Do not disconnect I/O-side wires or connectors
unless power has been switched off or the area is known
to be nonhazardous.
to be nonhazardous.
Caution
Do not remove modules unless power has been
switched off or the area is known to be nonhazardous.
Caution
Substitution of components may impair
suitability for Class I, Division 2.
Caution
For Zone 2 applications, install the system
in an enclosure rated to at least IP 54 as defined by
IEC 60529 and EN 60529.
IEC 60529 and EN 60529.
Caution
For Zone 2 applications, install a protection
device between the input signal and the NI 9201/9221
input terminal. The device must prevent the input
channel-to-COM voltage from exceeding 85 V if there is
a transient overvoltage condition.
input terminal. The device must prevent the input
channel-to-COM voltage from exceeding 85 V if there is
a transient overvoltage condition.
Special Conditions for Hazardous Locations Use in Europe
This equipment has been evaluated as EEx nC IIC T4 equipment
under DEMKO Certificate No. 03 ATEX 0324020X. Each module
is marked
under DEMKO Certificate No. 03 ATEX 0324020X. Each module
is marked
II 3G and is suitable for use in Zone 2 hazardous