Using the Modbus RTU Protocol
 9300 Series User’s Guide
Page 56
Chapter 3 - Default Meter Functionality 
Modbus Slave Module #1                               Modbus Slave Module #2
Modbus Slave Module #3                               Modbus Slave Module #4
Modbus Slave Module Parameter Mapping
The following tables show which measurements are provided by each of the four 
Modbus Slave modules. The source for each measurement is shown (“Source ION 
Module”) so that you can easily delete parameters if you want to access different 
data. Note that the Modbus Register remains the same if you link a different 
parameter into one of the Modbus Slave module inputs (i.e. any value you link to 
Modbus Slave module #1, Source Input #1 will use Modbus Register 40011).
Modbus Slave Module #1 Links
Setup Register
Setting
Setup Register
Setting
Format
unsigned 16-bit
Format
signed 32-bit
Base Address
40011
Base Address
40027
Scaling
YES
Scaling
YES
In Zero
0
In Zero
-214748364
In Full
6553
In Full
214748364
Out Zero
0
Out Zero
-2147483640
Out Full
65530
Out Full
2147483640
Setup Register
Setting
Setup Register
Setting
Format
signed 32-bit
Format
signed 32-bit M10K
Base Address
40059
Base Address
40089
Scaling
YES
Scaling
NO
In Zero
-214748364
In Full
214748364
Out Zero
-2147483640
Out Full
2147483640
Measurement 
Label
Source ION Module
Modbus Module and Input Number
Modbus Register
L-N Voltage Phase A
Vln a
Power Meter
Modbus Slave #1 – Source Input #1
40011
L-N Voltage Phase B
Vln b
Power Meter
Modbus Slave #1 – Source Input #2
40012
L-N Voltage Phase C
Vln c
Power Meter
Modbus Slave #1 – Source Input #3
40013
Average L-N Voltage
Vln avg
Power Meter
Modbus Slave #1 – Source Input #4
40014
L-L Voltage AB
Vll ab
Power Meter
Modbus Slave #1 – Source Input #5
40015
L-L Voltage BC
Vll bc
Power Meter
Modbus Slave #1 – Source Input #6
40016
L-L Voltage CA
Vll ca
Power Meter
Modbus Slave #1 – Source Input #7
40017