Improving Control Accuracy
IMPROVING CONTROL ACCURACY
Temp
Maximum
Time
Variance
VAr
°
hi
°
±
0.1
°
Minimum
Lo
°
The following functions are to assist engineers with
machine development, commissioning and troubleshooting.
READ SP1 OUTPUT PERCENTAGE POWER
Poor control may be due to incorrectly sized heaters.
SP1.P
(Level 2) constantly displays the output
percentage power applied, which at normal setpoint
should ideally be within 20 - 80% to achieve stable
control.
CONTROL ACCURACY MONITOR
This measures the control stability, to within 0.1 °C/°F.
The monitor is started using 
CheK 
(Level 3) and the
variance (deviation), maximum and minimum temperature
are displayed and constantly updated in
Using the 
CheK 
Control accuracy monitor
To start the monitor select
Note:
During monitoring either return to normal operation 
or remain in program mode.
To view monitor readings: index to
The lower display will alternate between
Var°
and the variance displayed in degrees (e.g. 0.6)
Press and hold ✱ and press ▲ once, the lower display will
alternate between 
VAr°
and the maximum
hi°
displayed
in degrees (e.g. 320.3)
Press and hold ✱ and press ▲ once, the lower display will
alternate between 
VAr°
and the minimum 
Lo°
displayed
in degrees (e.g. 319.7)
CheK oFF
stops monitor retaining readings
CheK on
resets readings.
On de-powering 
CheK 
resets to 
oFF
and  
rEAd 
is zeroed.