Function List
LEVEL 2
F
unction      Options
[Factory settings] shown in brackets
MANUAL CONTROL MODES
0 to 100 %     ‘read only’
Read SP1 output percentage power
[oFF]  1 to 100 % (not in ON/OFF)
SP1 manual percentage power control
For manual control should a sensor fail.
Record typical 
SP1.P values beforehand.
100 to 0 % duty cycle
[100]
Set SP1 power limit percentage
Limits maximum SP1 heating power during warm-up
and in proportional band.
100 to 0 % duty cycle 
[100]
Set SP2 percentage power limit (cooling)
SP2 OPERATING MODES (see page 12/13)
[nonE]   dV.hi  dV.Lo  bAnd    FS.hi   FS.Lo   Cool
Main SP2 operating mode
F
unction      Options
[Factory settings] shown in brackets
[nonE]    LtCh  hoLd   nLin
Subsidiary SP2 mode: latch/sequence
Non-linear cool proportional band
INPUT SELECTION AND RANGING
[1]     0.1
Select display resolution: for display of process
temperature, setpoint,
OFSt, Set.2, hi.SC, LoSC
.
sensor minimum [sensor maximum]
°C/°F
Set full scale
[sensor minimum] sensor maximum
°C/ºF
Set scale minimum (default 0°C or 32°F)
Select input sensor  
[nonE]
(See SENSOR SELECTION table, page 31)
[nonE]  °C   °F  bAr   Psi  Ph  rh SEt
Select °C/°F or process units
18
SP1.P
HAND
PL.1
PL.2
SP2.A
DISP
HISC
LO.SC
INPT
UNIT
SP2.B