Hardware operation 
3.2 Operating the inverter 
15 
3.2.5 Fault 
reset 
You can reset a fault by turning the keyswitch from "AUTO" to "TEST" and back to "AUTO" or vice versa. 
If the inverter has been disabled due to a fault, it can now be activated again. 
 
3.2.6  Displaying currently active alarms and faults 
In Automatic mode, you can display the last ten alarm and fault codes. To do this, press the OFF key in 
Automatic mode for more than 3 seconds. The alarm and fault codes will then appear in sequence on the 
two-digit display. 
 
3.2.7  Adjusting the voltage 
In Test mode, you can adjust the voltage at the DC connections for test and commissioning purposes. To 
do this, press the OFF key in Test mode for more than 3 seconds. The voltage is then adjusted in 
increments of 10°V across the entire voltage window. The two-digit display shows the first two digits of 
the DC voltage value (for example, 55 represents a voltage of 550 V DC). 
 
3.2.8  Grid LED indicator bar 
The grid LED indicator bar shows the power output of the inverter system in increments of 25%. The 
display refers to the output of the relevant individual inverter. In Automatic mode, the total system output 
of the master/slave unit is shown on the two-digit display. 
 
3.2.9 Status 
display 
The status display indicates the status of the whole system. 
 
Insulation fault/alarm (LED "ISO FAULT") 
If the insulation resistance between the PV field and ground is too low, there is a risk of electric shock if 
you touch the PV modules. The inverter is equipped with an insulation monitoring device which detects 
this hazard and outputs an alarm. 
If the insulation resistance is in the range that is dangerous for people, an insulation warning is triggered 
and the "ISO FAULT" LED flashes. 
If the insulation value is in the range that is dangerous for the system, the "ISO FAULT" LED lights 
continuously and the inverter releases the relevant inputs. Even when switched off, a system with an 
insufficient insulation value represents a danger. 
The cause of the low insulation value must be immediately rectified. 
 
DANGER 
 
The cause of the low insulation value must be immediately rectified. 
Even when switched off, a system with an insufficient insulation value represents a danger. 
 
CAUTION 
 
Insulation faults reduce system yield! 
The cause of the low insulation value must be immediately rectified. 
 
Ready to run (LED "ONLINE") 
The "ONLINE" LED lights up steadily while the inverter is in operation. The DC contactors and the main 
AC contactor are closed and the power unit is generating voltage.