Alarm and fault messages 
4.2 Alarm and fault messages  
31 
Table 4-3 Fault 0 
(Alarm) General fault on transformer 
Condition 
The hardware contact in the power unit has tripped. 
Causes 
There is a defect in the inverter. 
 
Measures 
Replace the affected components. 
Replace the drive. 
 
Table 4-4 Faults 1 and 33 
Message 1 (alarm): Inverter is signaling overtemperature, stage 1 
Fault 33 (alarm): Inverter is signaling overtemperature, stage 2 
Condition 
An excessive heatsink temperature in the inverter has 
been detected. 
The thermoclick circuit for the reactors and transformers 
has been interrupted. 
Cooling system is not working properly 
o
 
Drive fan is not running 
  Fan motor is defective 
  Start capacitor is defective 
  No power supply to fan 
 
USI is defective 
 
Infeed transformer is defective 
o
 
Heatsink is blocked 
o
 
Drive fan speed is too low 
  Infeed transformer is connected to tap 
460 V instead of 400 V 
Heat generation is exceeding tolerance 
o
 
Current is too high 
  Parameter setting error (CU software – 
current limit value) 
o
 
IGBT module defective 
Fault in measured-value sensing 
o
 
Temperature sensor in heatsink is defective 
o
 
Temperature sensor connection is defective 
o
 
CU data input is defective 
 
Causes 
Reactor or transformer is overheating (fault 33 only, 
without preceding warning level 1 in the PPsolar 
event memory) 
o
 
Cooling system is not working properly 
  Housing fans are not running  
  Fans are defective 
  Thermostat is defective 
  Thermostat is incorrectly set 
  Air intake is restricted 
  Air inlet grille on housing is clogged 
up 
  Air outlet is restricted