SJ300 Inverter Specifications
Geting Star
ted
1–8
Tables for 400V class inverters, continued...
Footnotes for the preceding tables and the table that follows:
Note 1: The protection method conforms to JEM 1030.
Note 2: The applicable motor refers to Hitachi standard 3-phase motor (4-pole). When using
Note 2: The applicable motor refers to Hitachi standard 3-phase motor (4-pole). When using
other motors, care must be taken to prevent the rated motor current (50/60 Hz) from
exceeding the rated output current of the inverter.
exceeding the rated output current of the inverter.
Note 3: The output voltage decreases as the main supply voltage decreases (except when
using the AVR function). In any case, the output voltage cannot exceed the input
power supply voltage.
power supply voltage.
Note 4: To operate the motor beyond 50/60 Hz, consult the motor manufacturer for the
maximum allowable rotation speed.
Note 5: When SLV is selected, please set the carrier frequency higher than 2.1 kHz.
Note 6: At the rated voltage when using a Hitachi standard 3-phase, 4-pole motor (when
Note 6: At the rated voltage when using a Hitachi standard 3-phase, 4-pole motor (when
selecting sensorless vector control—SLV).
Note 7: The braking torque via capacitive feedback is the average deceleration torque at the
shortest deceleration (stopping from 50/60 Hz as indicated). It is not continuous
regenerative braking torque. The average decel torque varies with motor loss. This
value decreases when operating beyond 50 Hz. If a large regenerative torque is
required, the optional regenerative braking resistor should be used.
regenerative braking torque. The average decel torque varies with motor loss. This
value decreases when operating beyond 50 Hz. If a large regenerative torque is
required, the optional regenerative braking resistor should be used.
Note 8: The frequency command will equal the maximum frequency at 9.8V for input voltage
0 to 10 VDC, or at 19.6 mA for input current 4 to 20 mA. If this characteristic is not
satisfactory for your application, contact your Hitachi sales representative.
satisfactory for your application, contact your Hitachi sales representative.
Note 9: The storage temperature refers to the short-term temperature during transport.
Note 10: Conforms to the test method specified in JIS C0911 (1984). For the model types
Note 10: Conforms to the test method specified in JIS C0911 (1984). For the model types
excluded in the standard specifications, contact your Hitachi sales representative.
Note 11: NEMA 1 applies up to 22kW. An optional wire-entry conduit box is required for
30kW to 55kW models to meet NEMA 1 rating.
Item
400V Class Specifications
SJ300 inverters,
400V models
400V models
UL version
750HFU
900HFU
1100HFU
—
1500HFU
CE version
750HFE
900HFE
1100HFE
1320HFE
—
Applicable motor size *2
HP
100
125
150
175
200
kW
75
90
110
132
150
Rated capacity (400 / 480V) kVA
103.2 / 123.8
121.9 / 146.3
150.3 / 180.4
180.1 / 216.1
180.1 / 216.1
Rated input voltage
3-phase (3-wire) 380 to 480V ±10%, 50/60 Hz ±5%
Rated input current (A)
164
194
239
286
286
Rated output voltage *3
3-phase (3-wire): 380 to 480V (corresponding to input voltage)
Rated output current (A)
149
176
217
260
260
Efficiency at 100% rated output, %
95.2
95.2
95.2
95.2
95.2
Watt loss,
approximate (W)
approximate (W)
at 70% output
2675
3375
3900
4670
4670
at 100% output
3800
4800
5550
6650
6650
Starting torque *6
180% at 0.5 Hz (SLV), 130% at around 0 Hz (SLV, 0 Hz domain,
with motor one frame size down), 100% at 0 Hz (with feedback board)
Dynamic braking
approx. % torque,
short time stop *7
approx. % torque,
short time stop *7
w/o braking unit
10%
with braking unit
45–70%
40–60%
30–50%
25–40%
20–35%
DC braking
Variable operating frequency, time, and braking force
Weight
kg / lb
60 / 132
60 / 132
80 / 176
80 / 176
80 / 176