29 
The two diagrams below show input wiring circuits using an external supply. If using the 
“Sinking Inputs, External Supply” in below wiring diagram, be sure to remove the jumper 
wire, and use a diode (*) with the external supply. This will prevent a power supply 
contention in case the jumper wire is accidentally placed in the incorrect position. For the 
“Sourcing Inputs, External Supply”, please connect the jumper wire as drawn in the 
diagram below. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Sinking Inputs, External Supply 
Jumper wire
 = Removed 
GND
Field device 
Open collector outputs, 
NPN transistors 
WJ200 
P24 
1
7
24V 
PLC 
Input 
circuits
-
Logic GND 
Input common
Input switches
L
24V 
-
-
24V 
*
* Note: Make sure to remove the j
umper wire
 in case of using
an external power supply. 
Sourcing Inputs, External Supply 
Jumper wire
 = Removed 
Field device 
WJ200 
P24 
1
7
24V 
PLC 
Input 
circuits
-
Input common
Input switches
L
GND
PNP transistor 
sourcing outputs 
24V 
-
24V
+
-