 Fuse Sizes
 
Distribution fuse size marking is included in the manual to indicate that the unit shall be 
connected with a Listed Cartridge Nonrenewable fuse, rated 600 Vac with the current ratings as 
shown in the table below or Type E Combination Motor Controller marking is included in the 
manual to indicate that the unit shall be connected with,LS Industrial System Co.,Ltd,Type E 
Combination Motor Controller MMS Series with the ratings as shown in the table below: 
 
Inverter Model 
Type 
Fuse Rating 
Type E CMC 
WJ200-001S 
WJ200-002S 
WJ200-004S 
10A, AIC 200kA 
WJ200-007S 20A, 
AIC 
200kA 
WJ200-015S  
WJ200-022S 
30A, AIC 200kA 
MMS-32H,240V,40A 
WJ200-001L 
WJ200-002L 
WJ200-004L  
10A, AIC 200kA 
WJ200-007L 
WJ200-015L 
15A, AIC 200kA 
WJ200-022L 20A, 
AIC 
200kA 
WJ200-037L  
30A, AIC 200kA 
MMS-32H,240V,40A 
WJ200-055L 
WJ200-075L 
60A, AIC 200kA 
WJ200-110L 
WJ200-150L 
80A, AIC 200kA 
MMS-100H,240V,80A 
WJ200-004H 
WJ200-007H 
WJ200-015H 
WJ200-022H 
10A, AIC 200kA 
WJ200-030H 
WJ200-040H 
15A, AIC 200kA 
WJ200-055H 
WJ200-075H 
30A, AIC 200kA 
WJ200-110H 
WJ200-150H 
Class J 
50A, AIC 200kA 
MMS-32H,480V,40A 
or 