National Instruments FP-AI-112 用户手册

下载
页码 16
© National Instruments Corp.
3
FP-AI-112 and cFP-AI-112
3. Using a number 2 Phillips screwdriver with a shank of at least 
64 mm (2.5 in.) length, tighten the captive screws to 1.1 N
⋅ m 
(10 lb
⋅ in.) of torque. The nylon coating on the screws prevents 
them from loosening.
 
Figure 2.  Installing the cFP-AI-112
Wiring the [c]FP-AI-112
The FP-TB-x terminal base has connections for each of the 
16 input channels and for an optional external power supply to 
power field devices. The cFP-CB-x connector block provides the 
same connections. Each channel has one input terminal (V
IN
) for 
voltage input. All 16 inputs are referenced to the COM terminals, 
which are internally connected to each other and to the C terminals. 
The channels share eight V
SUP
 terminals, all of which are internally 
connected to each other and to the V terminals.
1
cFP-AI-112
2
Captive Screws
3
cFP Controller Module
4
Screw Holes
5
cFP Backplane
2
2
1
3
5
4
4