Planning Preparations
Th
is g
u
id
e for use 
by 
qu
alified 
perso
nnel
 o
n
ly.
DC Components
Batteries
The Freedom SW 230V system requires a 24-volt, lead-acid deep-
cycle battery or group of batteries to provide the DC current that the 
inverter/charger converts to AC power. The battery may be a 
flooded, gel, or AGM type. 
Estimating the battery size that will meet your requirements.
Designing battery banks.
Restrictions on the size of appliances. 
For detailed information about specific brands of batteries, consult 
individual battery manufacturers.
DC Cabling
Definition
DC cabling includes all of the cables and connectors 
between the batteries, the DC disconnect and overcurrent protection 
device, and the inverter/charger. 
Type
All installations require multi-strand insulated cables. The 
DC cables must be copper and must be rated 75°C minimum. In 
Australia, they must be rated 90°C minimum.
Size and Length
See Table 2 for required DC cable length and 
cable size and Table 3 for required fuse size for the Freedom SW 
230V. Wire size is usually marked on the cables. 
Table 2 Minimum Recommended Battery Cable
a
 Sizes 
a. Copper conductors with thermoplastic insulation rated at 75C or higher. In Australia, 
thermoplastic insulation must be rated at 90C or higher.
Conduit (Free Air)
Model
Typical 
Amps
(A)
Cable Length
< 1.5 m
Cable Length
1.5 to 3.0 m
Freedom SW 2524-230
140
50 mm
2
 (25 mm
2
)
70 mm
2
 (35 mm
2
)
Freedom SW 3524-230
200
240 mm
2
 (120 mm
2
)
300 mm
2
 (150 mm
2
)
IMPORTANT: Longer cables may cause the inverter to shut down under 
a heavy load.
FIRE HAZARD
Undersized cables will overheat. Consult local electrical codes to 
determine minimum required size.
Failure to follow these instructions can result in death or serious 
injury.