FieldServer FS-8700-21 用户手册

下载
页码 62
FS-8700-21 LonWorks Manual 
 
 
 
 
 
 
 
Page 19 of 62 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA   Web: www.fieldserver.com 
Tel: (408) 262 2299   Fax: (408) 262 2269   Toll Free: (888) 509 1970   email: support@fieldserver.com 
6.2.5  Map Descriptor Example 1 - Explicit Configuration using Network Management  Polls 
The Map Descriptor pollTemp_p shows the use of SNVT_Units for Scaling when polling temperature 
The Map Descriptor pollSwitch shows the use of SNVT_Option for Selective data scanning. This only brings in the “State” portion of SNVT_Switch 
Map_Descriptors 
 
 
 
 
 
 
 
 
 
 
Map_Descriptor_Name   ,Data_Array_Name   ,Data_Array_Offset   ,Lon_Function   ,Function   ,Node_Name    
,SNVT_Index   ,SNVT_Type    
,SNVT_Units   ,SNVT_Option   ,Scan_Interval 
pollTemp_p           
,DA_Explicit      
,1 
,NMFETCHC       ,Rdbc      
,Remote_Node   ,0 
,SNVT_temp_p   ,Deg_F       
,-            
,1.0s 
pollSwitch           
,DA_Explicit      
,2 
,NMFETCHC       ,Rdbc      
,Remote_Node   ,1 
,SNVT_switch  
,-           
,State        
,1.0s 
 
 
 
 
6.2.6  Map Descriptor Example 2 – Polling UNVT’s 
Map_Descriptors 
 
 
 
 
 
 
 
 
 
 
Map_Descriptor_Name   ,Data_Array_Name   ,Data_Array_Offset   ,Lon_Function   ,Function   ,Node_Name    
,SNVT_Index   ,SNVT_Type   ,UNVT_Byte_Length   ,Scan_Interval 
 
pollUNVT             
,DA_Explicit      
,101 
,NMFETCHC       ,Rdbc      
,Remote_Node   ,2 
,UNVT       
,31 
,1.0s 
 
 
 
Explicitly Addressed Client Map Descriptors use 
this field to point to their relevant Server Map 
Descriptors. 
For Non-Throttled 
Client Map 
Descriptors the 
Scan_Interval 
determines the 
update rate. 
This field 
determines the 
Map 
Descriptor’s 
function. See 
Section 6.1.2 
for more 
information. 
UNVT Byte length must be specified for correct 
operation.